| Plan Review Notes For Permit 18050170 |
| Permit Number |
18050170 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-03 18:04:27 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. INSTALLATION SCHEDULE EDGE DISTANCE STATES "NA". | | | THIS INFORMATION IS REQUIRED. NOTE THAT PAGE 13 HAS A | | | TABLE OF FACTORS FOR REDUCED EDGE DISTANCE. PROPOSED | | | SPACING MAY NOT COMPLY DEPENDING ON EDGE DISTANCE. | | | | | | FOR TAPCONS, EDGE DISTANCE LESS THAN 3" REQUIRES A .35 | | | FACTOR APPLIED TO THE SPACING WHICH IS NOT POSSIBLE FOR | | | THE OPTIONS SELECTED. FBC R 301. | | | |
|