| 2018-05-14 07:09:47 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1.PLAN IS NOT LEGIBLE, PLEASE PROVIDE TWO SETS OF |
| | LEGIBLE PLANS. |
| | |
| | 2. PLAN HAS LANGUAGE REGARDING PLYWOOD; NOT CLEAR WHAT |
| | THIS IS. IF YOU ARE PROPOSING WORK IN THE BUILDING |
| | ENVELOPE OTHER THAN WINDOW INSTALLATION, INCLUDE |
| | SPECIFICATION, SCOPE, WIND DESIGN CRITERIA (MINIMUM |
| | 170MPH EXPOSURE C), AND INCLUDE THE PRINTED NAME OF THE |
| | INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN FBC |
| | 107. |
| | |
| | BASED ON PREVIOUS COMMENT #3, STUCCO REPAIRS ARE |
| | PROPOSED. REVISE SPECIFICATION - INSTALLATION OF |
| | PLYWOOD ON THE EXTERIOR IS NOT A COMPLETE SPECIFICATION |
| | THAT COMPLIES WITH THE FBC. |
| | |
| | 2. ONE SET OF PRODUCT APPROVALS FOR A WINDOW AND |
| | SHUTTER WAS PROVIDED. TWO SETS ARE REQUIRED, AND FOR |
| | THE SHUTTERS, COMPLETE THE "SCHEDULE FOR INSTALLATION |
| | OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL |
| | INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL |
| | SPREADSHEET): |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS?PAGE=2 |
| | |
| | 3. COMMENT FROM PREVIOUS LIST: REVISE PLAN, WHAT IS THE |
| | SUBSTRATE UNDER THE STUCCO WHERE STUCCO REPAIRS ARE |
| | PROPOSED? |
| | IF THIS IS FRAME, WHAT IS THE EXTENT OF THE REPAIR? A |
| | DETAIL AND PREINSPECTION MAY BE REQUIRED. |
| | |
| | 2ND REVIEW, PLYWOOD IS NOTED, WHICH IMPLIES WOOD FRAME. |
| | REVISE THE PLAN TO PROVIDE A DETAIL. SCOPE OF "STUCCO |
| | REPAIR" IS STILL NOT CLEAR. WAS STUCCO INSTALLED OVER |
| | STUCCO, WAS SHEATHING REPLACED, WAS A BOND BREAK |
| | INSTALLED? SCOPE AND COMPLIANCE WITH FBC NOT CLEAR. |
| | |
| | PLAN STATES THAT THE WORK WAS DONE BY OTHERS. ALL |
| | INFORMATION THAT WOULD HAVE BEEN REQUIRED IF THE WORK |
| | WAS NOT YET DONE IS REQUIRED. |
| | |
| | |