| Permit Number |
18050155 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-03 17:46:46 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. REVISE PLAN TO SHOW LOCATION AND SIZE OF PROPOSED | | | WINDOW REPLACEMENT. ALSO CLARIFY; APPLICATION STATES | | | "REPAIR / REPLACE REAR WINDOW". IS A REPLACEMENT | | | PROPOSED, OR REPAIR? A REPAIR DOES NOT TYPICALLY | | | REQUIRE A PERMIT, REPLACEMENT DOES. A PRODUCT APPROVAL | | | WAS SUBMITTED SO IT APPEARS THAT A REPLACEMENT IS | | | PROPOSED. | | | | | | 2. REVISE PLAN TO INCLUDE TOTAL AGGREGATE AREA OF | | | GLAZING, PROPOSED NON IMPACT AREA OF GLAZING, FBC EB | | | 707.4. | | | | | | 3. REVISE PLAN, WHAT IS THE SUBSTRATE UNDER THE STUCCO | | | WHERE STUCCO REPAIRS ARE PROPOSED? | | | IF THIS IS FRAME, WHAT IS THE EXTENT OF THE REPAIR? A | | | DETAIL AND PREINSPECTION MAY BE REQUIRED. | | | |
|