| Plan Review Notes For Permit 18050129 |
| Permit Number |
18050129 |
|
| Review Stop |
SIGNATURE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-22 10:22:39 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. CURB DETAIL AND CALCULATIONS PREPARED BY BOWDOIN G | | | HUTCHINSON, PE IS NOT DIGITALLY SIGNED AND SEALED. | | | PROVIDE A PAPER ORIGINAL, FS471 OR A DIGITALLY SIGNED | | | AND SEALED DOCUMENT. | | | | | | 2. ROOF CALCS PREPARED BY ALBERTO CARDONA, PE IS NOT | | | DIGITALLY SIGNED AND SEALED. PROVIDE A PAPER ORIGINAL, | | | FS471 OR A DIGITALLY SIGNED AND SEALED DOCUMENT. | | | | | | 3. AC STAND ENGINEERING PREPARED BY DENIS K. SOLANO, PE | | | ARE NOT DIGITALLY SIGNED AND SEALED. PROVIDE A PAPER | | | ORIGINAL, FS471 OR A DIGITALLY SIGNED AND SEALED | | | DOCUMENT. | | | | | | |
|