2018-05-22 10:15:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PAGE S0.2 WIND DIAGRAM DOES NOT INCLUDE A FLAT ROOF,
 AND PRESSURES ON THAT PAGE ARE TOO LOW FOR A FLAT ROOF.
 CLARIFY LOCATION WHERE THE CERTAINTEED MODIFIED IS
 PROPOSED, FBC 107, FBC B 1609.
  
 2. THE ASSEMBLY PROPOSED (#11, PAGE 7 OF 10) FOR THE
 SLOPE ROOF UNDERLAYMENT HAS A LIMITATION OF -75PSF;
 SHEETS S0.2 REQUIRES -97.56 FOR THE OVERHANG ZONE.
  
 3. THE ENGINEER'S REVIEW STAMP COVERS SOME OF THE
 INFORMATION ON THE AC STAND ENGINEERING; PROVIDE A
 CLEAN COPY.
  
 4. AC STAND, INDICATE WHICH OPTION IS PROPOSED. ALSO
 PROVIDE INFORMATION REGARDING THE UNIT TO SHOW
 COMPLIANCE WITH FBC B 1510.10 (CLEARANCE).
  
 5. EUROWALL, INDICATE WHICH PANEL WIDTH IS PROPOSED,
 FBC B 1609. DP IS TO COMPLY WITH DESIGN PRESSURES
 SPECIFIED ON SHEET S0.2.
  
  
  
  
  