| Notes |
| Date |
Text |
| 2018-05-17 13:08:31 | 1) SHT. RF1.1 - SUBMIT CALCULATIONS FOR THE SIZING OF | | | THE GUTTER SYSTEM FOR THE RAINWATER.HOW DID YOU ARRIVE | | | AT THE 106 GPM REQUIRED NUMBER?/ | | | 2) SHT. RF1.1 - SUBMIT CALCULATIONS FOR THE SIZING OF | | | THE DOWNSPOUTS. HOW DID YOU REACH THE REQUIRED CAPACITY | | | NUMBER OF 192 GPM? | | | 3) SHT. RF.1.1 - ROOF STORM DRAIN SCHEDULE --SUBMIT | | | ADDITIONAL INFORMATION AS TO HOW YOU ARRIVED AT THE | | | NUMBER OF DOWNSPUTS REQD. (2) 3" DOWNSPOUTS DO NOT | | | EQUAL THE SQUARE INCH AREA OF A 6" DOWNSPOUT NOR DO (3) | | | 3" DOWNSPOUTS EQUAL THE SQUARE INCH AREA OF A | | | 9"DOWNSPOUT. | | | 4) SUBMIT A SITE PLAN SHOWING WHERE AND HOW THE STORM | | | DRAINS CONNECT TO THE STORM SEWER. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | |
|