Plan Review Notes
Plan Review Notes For Permit 18050094
Permit Number 18050094
Review Stop P
Sequence Number 1
Notes
Date Text
2018-05-17 13:08:311) SHT. RF1.1 - SUBMIT CALCULATIONS FOR THE SIZING OF
 THE GUTTER SYSTEM FOR THE RAINWATER.HOW DID YOU ARRIVE
 AT THE 106 GPM REQUIRED NUMBER?/
 2) SHT. RF1.1 - SUBMIT CALCULATIONS FOR THE SIZING OF
 THE DOWNSPOUTS. HOW DID YOU REACH THE REQUIRED CAPACITY
 NUMBER OF 192 GPM?
 3) SHT. RF.1.1 - ROOF STORM DRAIN SCHEDULE --SUBMIT
 ADDITIONAL INFORMATION AS TO HOW YOU ARRIVED AT THE
 NUMBER OF DOWNSPUTS REQD. (2) 3" DOWNSPOUTS DO NOT
 EQUAL THE SQUARE INCH AREA OF A 6" DOWNSPOUT NOR DO (3)
 3" DOWNSPOUTS EQUAL THE SQUARE INCH AREA OF A
 9"DOWNSPOUT.
 4) SUBMIT A SITE PLAN SHOWING WHERE AND HOW THE STORM
 DRAINS CONNECT TO THE STORM SEWER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW