Plan Review Notes
Plan Review Notes For Permit 18050079
Permit Number 18050079
Review Stop E
Sequence Number 1
Notes
Date Text
2018-05-22 15:30:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL LA. NEC 225.31,
 225.32
 2. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 3. NOTE 1 ON SHEETS E-2 AND E-3 DOES NOT ADDRESS THE
 AFCI REQUIREMENTS PER THE 2014 NEC. ALL BRANCH CIRCUITS
 THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 4. NOTE 2 ON SHEETS E-2 AND E-3 STATES THAT RECEPTACLES
 SHALL BE TR PER THE 2011 NEC, WHICH IS NOT THE CURRENT
 CODE. PROVIDE CORRECTION. FBC PREFACE.
 5. RISER DIAGRAM SHOWS THE PANELS AS 10K AIC RATED,
 WHILE THE PANEL SCHEDULES SHOWS THEM AS 22K AIC RATED.
 CORRECT DISCREPANCY. WPB FBC 107.2.1
 6. GFCI PROTECTION IS REQUIRED FOR ALL OUTLETS IN
 GARAGE INCLUDING THE GARAGE DOOR OPENER. PROVIDE
 CORRECTION. NEC 210.8; FBC RE E3902.2
 7. GFCI RECEPTACLES IN GARAGE ARE SHOWN ON THE SAME
 CIRCUIT AS ITEMS LOCATED OUTSIDE OF GARAGE. PROVIDE
 CORRECTION. NEC 210.52(G)(1); FBC RE E3901.9
 8. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC
 210.8(D); FBC RE E3902.10
 9. LIGHTING OVER TUB/SHOWERS APPEARS TO BE A STANDARD
 RECESS LIGHT. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL
 BE SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE E4003.11
 10. PROVIDE GFCI WEATHER PROOF RECEPTACLE ON BALCONY
 AND TERRARE AREAS. NEC 210.52(E); FBC RE E3901.7
 11. BREAKER FOR POOL PUMP REQUIRED TO BE GFCI
 PROTECTED. PROVIDE CORRECTION. NEC 680.21(C); FBC RE
 E4203.1.3
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  