2019-06-11 08:44:03PLUMBING PROVISO:
  
 REVISE PLAN TO COMPLY WITH THE FOLLOWING COMMENTS:
  
  
 4. AAV ARE NOT ALLOWED AS VENTS BELOW THE 4TH BRANCH
 DOWN FROM THE TOP OF THE STACK UNLESS PROVIDED WITH A
 RELIEF VENT . PER FBC PL 918.3.1
  
 5. FLOOR DRAINS SHALL HAVE TRAP PRIMERS SHOW ON
 ISOMETRIC DRAWING. PER FBC PL 1002.4.1
  
 6. WYE STRAINERS ARE REQUIRED ON PRV PROVIDE DETAIL.
 PER FBC PL 604.8
  
 7. PLACE NOT ON PLAN A SEPARATE PERMIT IS REQUIRED FOR
 BACKFLOW AT WATER METER. WPB UTILITIES DEPT.
  
 8. THE NOTE ON THE PLAN FOR THE ELEVATOR SUMP PUMP IS
 REFERENCING A DETAIL I COULD NOT LOCATE ON ON THE PLAN
 PLEASE PROVIDE DETAIL AND MANUFACTURE SPECIFICATIONS
 WITH OIL MINDER OR DRAIN THROUGH OIL INTERCEPTOR. PER
 FBC PL 1003.4
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER