| Plan Review Notes For Permit 18050056 |
| Permit Number |
18050056 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2019-06-11 08:44:03 | PLUMBING PROVISO: | | | | | | REVISE PLAN TO COMPLY WITH THE FOLLOWING COMMENTS: | | | | | | | | | 4. AAV ARE NOT ALLOWED AS VENTS BELOW THE 4TH BRANCH | | | DOWN FROM THE TOP OF THE STACK UNLESS PROVIDED WITH A | | | RELIEF VENT . PER FBC PL 918.3.1 | | | | | | 5. FLOOR DRAINS SHALL HAVE TRAP PRIMERS SHOW ON | | | ISOMETRIC DRAWING. PER FBC PL 1002.4.1 | | | | | | 6. WYE STRAINERS ARE REQUIRED ON PRV PROVIDE DETAIL. | | | PER FBC PL 604.8 | | | | | | 7. PLACE NOT ON PLAN A SEPARATE PERMIT IS REQUIRED FOR | | | BACKFLOW AT WATER METER. WPB UTILITIES DEPT. | | | | | | 8. THE NOTE ON THE PLAN FOR THE ELEVATOR SUMP PUMP IS | | | REFERENCING A DETAIL I COULD NOT LOCATE ON ON THE PLAN | | | PLEASE PROVIDE DETAIL AND MANUFACTURE SPECIFICATIONS | | | WITH OIL MINDER OR DRAIN THROUGH OIL INTERCEPTOR. PER | | | FBC PL 1003.4 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|