Plan Review Notes For Permit 18050056
Permit Number 18050056
Review Stop P
Sequence Number 4
Notes
Date Text
2019-06-10 13:10:433RD REVIEW: 18050056
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PREVIOUS PLUMBING COMMENTS NOT COMPLIED WITH : COMMENT
 #1 WILL HAVE TO BE COMPLIED WITH BEFORE I CAN PROVISO
 THE PLAN I SUGGEST A MEETING SO THAT WE CAN RESOLVE
 THIS, SEE MY CONTACT INFO BELOW.
  
 1. SHT. A208 DETAIL #1 THE GROUND FLOOR UNIT SHALL HAVE
 A BATHROOM THAT MEETS THE FHA REQUIREMENTS OF EITHER
 SPEC A OR B THE DETAIL DOES NOT SHOW THIS AND IT IS
 UNCLEAR WHAT THE NOTES FOR THE CLEAR FLOOR SPACE AND
 THE OFFSET LAVATORY ARE REFERRING TO IN THE ROOM NEXT
 TO THE BATHE ROOM IT IS LABELED GUEST BATH AND POWDER
 AND IT SHOWS THE ABBREVIATIONS FOR THE A SHOWER 2
 LAVATORY'S AND 2 TOILETS PLEASE CLARIFY. CLEARLY SHOW
 THE CLEAR FLOOR SPACE FOR THE TOILET , LAVATORY AND A
 PARALLEL FLOOR SPACE FOR THE SHOWER TO COMPLY WITH FHA
 GUIDELINES REQ #7 FIG #6
  
 THE FHA REQUIRES THE PRIMARY ENTRY LEVEL TO A MULTI
 STORIED DWELLING UNIT TO HAVE A USABLE BATHROOM AND
 KITCHEN ON THE SAME LEVEL. THE SPEC B BATHROOM ON THE
 2ND FLOOR DOES NOT MEET THIS REQUIREMENT THE FACT THAT
 THE USABLE BATHROOM ON THE 2ND FLOOR CAN NOT BE
 ACCESSED BY THE OCCUPANT EXCEPT BY EXISTING THE UNIT
 AND USING THE COMMON ELEVATOR TO REACH IT. FOR FURTHER
 GUIDANCE ON THIS DESIGN IT MIGHT BE HELPFUL TO CONTACT
 FAIR HOUSING FIRST SPEAK TO AMBER @ 888-341-7781 OR
 THEIR WEBSITE HTTPS://WWW.FAIRHOUSINGFIRST.ORG/
  
  
  
  
 4. AAV ARE NOT ALLOWED AS VENTS BELOW THE 4TH BRANCH
 DOWN FROM THE TOP OF THE STACK UNLESS PROVIDED WITH A
 RELIEF VENT . PER FBC PL 918.3.1
  
 5. FLOOR DRAINS SHALL HAVE TRAP PRIMERS SHOW ON
 ISOMETRIC DRAWING. PER FBC PL 1002.4.1
  
 6. WYE STRAINERS ARE REQUIRED ON PRV PROVIDE DETAIL.
 PER FBC PL 604.8
  
 7. PLACE NOT ON PLAN A SEPARATE PERMIT IS REQUIRED FOR
 BACKFLOW AT WATER METER. WPB UTILITIES DEPT.
  
 8. THE NOTE ON THE PLAN FOR THE ELEVATOR SUMP PUMP IS
 REFERANCING A DETAIL I COULD NOT LOCATE ON ON THE PLAN
 PLEASE PROVIDE DETAIL AND MANUFACTURE SPECIFICATIONS
 WIT OIL MINDER ON DRAIN THROUGH OIL INTERCEPTOR. PER
 FBC PL 1003.4
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]