| 2019-06-10 13:10:43 | 3RD REVIEW: 18050056 |
| | |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PREVIOUS PLUMBING COMMENTS NOT COMPLIED WITH : COMMENT |
| | #1 WILL HAVE TO BE COMPLIED WITH BEFORE I CAN PROVISO |
| | THE PLAN I SUGGEST A MEETING SO THAT WE CAN RESOLVE |
| | THIS, SEE MY CONTACT INFO BELOW. |
| | |
| | 1. SHT. A208 DETAIL #1 THE GROUND FLOOR UNIT SHALL HAVE |
| | A BATHROOM THAT MEETS THE FHA REQUIREMENTS OF EITHER |
| | SPEC A OR B THE DETAIL DOES NOT SHOW THIS AND IT IS |
| | UNCLEAR WHAT THE NOTES FOR THE CLEAR FLOOR SPACE AND |
| | THE OFFSET LAVATORY ARE REFERRING TO IN THE ROOM NEXT |
| | TO THE BATHE ROOM IT IS LABELED GUEST BATH AND POWDER |
| | AND IT SHOWS THE ABBREVIATIONS FOR THE A SHOWER 2 |
| | LAVATORY'S AND 2 TOILETS PLEASE CLARIFY. CLEARLY SHOW |
| | THE CLEAR FLOOR SPACE FOR THE TOILET , LAVATORY AND A |
| | PARALLEL FLOOR SPACE FOR THE SHOWER TO COMPLY WITH FHA |
| | GUIDELINES REQ #7 FIG #6 |
| | |
| | THE FHA REQUIRES THE PRIMARY ENTRY LEVEL TO A MULTI |
| | STORIED DWELLING UNIT TO HAVE A USABLE BATHROOM AND |
| | KITCHEN ON THE SAME LEVEL. THE SPEC B BATHROOM ON THE |
| | 2ND FLOOR DOES NOT MEET THIS REQUIREMENT THE FACT THAT |
| | THE USABLE BATHROOM ON THE 2ND FLOOR CAN NOT BE |
| | ACCESSED BY THE OCCUPANT EXCEPT BY EXISTING THE UNIT |
| | AND USING THE COMMON ELEVATOR TO REACH IT. FOR FURTHER |
| | GUIDANCE ON THIS DESIGN IT MIGHT BE HELPFUL TO CONTACT |
| | FAIR HOUSING FIRST SPEAK TO AMBER @ 888-341-7781 OR |
| | THEIR WEBSITE HTTPS://WWW.FAIRHOUSINGFIRST.ORG/ |
| | |
| | |
| | |
| | |
| | 4. AAV ARE NOT ALLOWED AS VENTS BELOW THE 4TH BRANCH |
| | DOWN FROM THE TOP OF THE STACK UNLESS PROVIDED WITH A |
| | RELIEF VENT . PER FBC PL 918.3.1 |
| | |
| | 5. FLOOR DRAINS SHALL HAVE TRAP PRIMERS SHOW ON |
| | ISOMETRIC DRAWING. PER FBC PL 1002.4.1 |
| | |
| | 6. WYE STRAINERS ARE REQUIRED ON PRV PROVIDE DETAIL. |
| | PER FBC PL 604.8 |
| | |
| | 7. PLACE NOT ON PLAN A SEPARATE PERMIT IS REQUIRED FOR |
| | BACKFLOW AT WATER METER. WPB UTILITIES DEPT. |
| | |
| | 8. THE NOTE ON THE PLAN FOR THE ELEVATOR SUMP PUMP IS |
| | REFERANCING A DETAIL I COULD NOT LOCATE ON ON THE PLAN |
| | PLEASE PROVIDE DETAIL AND MANUFACTURE SPECIFICATIONS |
| | WIT OIL MINDER ON DRAIN THROUGH OIL INTERCEPTOR. PER |
| | FBC PL 1003.4 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |