| 2019-06-05 15:43:00 | BUILDING PROVISO |
| | APPROVED WITH THE FOLLOWING EXCEPTIONS: |
| | |
| | 1) SUBMIT REVISED LIFE SAFETY PLANS THAT SHOW THE BATH |
| | EXHAUST CHASES, THE DRYER EXHAUST CHASE AND THE |
| | REFRIGERANT LINE CHASE AS TWO HOUR FIRE RATED SHAFTS |
| | PER 713.4. |
| | |
| | 2) DEFERRED SUBMITTALS. FBC 107.3.4.1 SUBMIT THREE SETS |
| | OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE |
| | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE |
| | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING |
| | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES |
| | FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW |
| | (GLASS TYPES), STRUCTURAL MULLIONS, EXTERIOR DOORS, |
| | EXTERIOR LOUVERS, AC STANDS, ROOF VENTALATORS AND ROOF |
| | HATCHES. |
| | |
| | 3) DEFERRED SUBMITTALS. FBC 107.3.4 SUBMIT THREE SETS |
| | OF DOCUMENTS FROM DELEGATE ENGINEERS THAT HAVE BEEN |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD FOR THE GLASS GUARDS, THE METAL GUARDS AND |
| | HANDRAILS. |
| | |
| | 4) THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD |
| | AREA. IN ADDITION TO THE PRE-CONSTRUCTION ELEVATION |
| | CERTIFICATE, YOU ARE REQUIRED TO SUBMIT A CONSTRUCTION |
| | IN PROGRESS ELEVATION CERTIFICATE WHEN THE GROUND FLOOR |
| | SLAB IS TO BE POURED AND A FINAL ELEVATION CERTIFICATE |
| | WHEN THE BUILDING IS COMPLETE AND ALL OF THE EQUIPMENT |
| | IS IN PLACE. YOU WILL NOT BE ABLE TO GET A CERTIFICATE |
| | OF OCCUPANCY UNTIL THE FINAL ELEVATION CERTIFICATE HAS |
| | BEEN SUBMITTED AND APPROVED BY THIS OFFICE. |