| 2019-05-03 09:48:39 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18050056 |
| | 5/3/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2014 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2014 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2014 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2014 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2014 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THIS 3RD REVIEW ITEMIZES THE 1ST AND 2ND REVIEW COMMENT |
| | RESULTS. PLEASE NOTE THAT THE PREVIOUS REQUEST FOR A |
| | RESPONSE NARRATIVE WAS IGNORED AGAIN. NARRATIVES HELP |
| | TO EXPEDITE THE REVIEW PROCESS! |
| | |
| | |
| | 1ST REVIEW: |
| | |
| | 1) OK, COMPLIED. |
| | |
| | 2) NON-COMPLIANCE: REQUESTED VENTILATION CALCULATIONS |
| | NOT PROVIDED. PLEASE NOTE THAT AUTOMATICALLY CONTROLLED |
| | SHUTOFF DAMPERS ARE REQUIRED FOR THE O/A INTAKE DUCTS- |
| | SECTION C403.2.4.4 FBC EC. ENERGY CONSERVATION. |
| | |
| | 6) NON-COMPLIANCE: M-1, M-2, M-3: THE SIZES OF THE |
| | LINEAR DIFFUSERS AND GRILLS SHOWN ON THE PLAN APPEAR TO |
| | INCORRECT BECAUSE THE WIDTH MEASUREMENTS ARE SHOWN IN |
| | FEET INSTEAD OF INCHES. |
| | |
| | 9) PARTIAL COMPLIANCE: |
| | 1. THE SHAFT IN WHICH THE DUCT IS INSTALLED SHALL BE |
| | CONSTRUCTED AND FIRE-RESISTANCE RATED AS REQUIRED BY |
| | THE FLORIDA BUILDING CODE, BUILDING. |
| | 8 .EXHAUST FAN OPERATION SHALL BE MONITORED IN AN |
| | APPROVED LOCATION AND SHALL INITIATE AN AUDIBLE OR |
| | VISUAL SIGNAL WHEN THE FAN IS NOT IN OPERATION. |
| | 9. MAKEUP AIR SHALL BE PROVIDED FOR THE EXHAUST SYSTEM. |
| | 10 .A CLEANOUT OPENING SHALL BE LOCATED AT THE BASE OF |
| | THE SHAFT TO PROVIDE ACCESS TO THE DUCT TO ALLOW FOR |
| | CLEANING AND INSPECTION. THE FINISHED OPENING SHALL BE |
| | NOT LESS THAN 12"X12". |
| | |
| | 10) OK. (KITCHEN APPLIANCES AND EXHAUST HOOD SPEC |
| | SHEETS MAY BE DEFERRED SUBMITTALS. PLEASE NOTE ALL |
| | COOKING APPLIANCES SHALL BE LISTED AND LABELED AS |
| | HOUSE-HOLD TYPE FOR DOMESTIC USE. MAKE UP AIR FOR |
| | EXHAUST MAY BE REUIRED IN ACCORDANCE WITH SECTION 505.2 |
| | FBC M.) |
| | |
| | 11) OK. (COMPLETE WIND LOAD ENGINEERING INCLUDING NOA'S |
| | AND/OR PRODUCT APPROVALS FOR FANS, FAN CURBS, AND ROOF |
| | STANDS MAY BE DEFERRED SUBMITTALS. ALL SUBMITTALS SHALL |
| | BEAR THE APPROVAL STAMP OF THE EOR.) |
| | |
| | 2ND REVIEW: |
| | |
| | 1) NON-COMPLIANCE: FIRE-RATED SHAFTS ARE REQUIRED FOR |
| | THE MULTI-STORY TOILET AND DRYER EXHAUST DUCTS- SECTION |
| | 607.6 FBC M. |
| | |
| | 2) NON-COMPLIANCE: M-1: PROVIDE A SEQUENCE OF OPERATION |
| | FOR EF-4 IN THE FIRE PUMP ROOM. |
| | |
| | 3) NON-COMPLIANCE: M-1, M-2, M-3: THE TOILET ROOM |
| | SUPPLY DUCT IS SHOWN RUNNING THROUGH A FIRE-RATED |
| | TOILET EXHAUST SHAFT WHICH IS PROHIBITED - SEE NOTE #4 |
| | ON THE PLAN AND SECTION 607.7 FBC M. |
| | |
| | 4) OK. (COMPLETE ENGINEERING FOR INSTALLATION OF THE |
| | ROOF FANS MAY BE DEFERRED SUBMIITALS.) |
| | |
| | 5) NON-COMPLIANCE: M-5: THE REVISED AC SCHEDULE IS |
| | INDICATING THE INCORRECT MODEL NUMBER FOR AHU-2- PLEASE |
| | CORRECT.( AHU-2 TRANE MODEL TEM6AOC42 IS SHOWN TO HAVE |
| | THE SAME CAPACTIES IN THE SCHEDULE AS THE 3-TON TRANE |
| | MODEL TEM6AOC36). |
| | |
| | 6) OK, COMPLIED. |
| | |
| | 7) OK, COMPLIED. |
| | |
| | 8) NOT PROVIDED: THE AC LOAD CALCULATIONS SHALL BE |
| | PERFORMED IN ACCORDANCE WITH ACCA STANDARD 183 OR ACCA |
| | MANUAL N. THIS A COMMERCIAL MULTI-FAMILY PROJECT THAT |
| | EXCEEDS 3 STORIES- SEE SECTIONS 202, C403.2.1, |
| | C407.5.2.2, AND C406.5.2.3 FBC EC. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |