Plan Review Notes
Plan Review Notes For Permit 18050056
Permit Number 18050056
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2019-05-14 13:56:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 PREVIOUS COMMENT:
  
 4) THERE IS NO INDICATION OF ELEVATORS BEING EQUIPPED
 WITH A REGION 7 KEYWAY.
  
 CHAPTER 399 FLORIDA STATUTES. SECTION 399.15, SECTION
 17:
 REGIONAL EMERGENCY ELEVATOR ACCESS ?
 (1) IN ORDER TO PROVIDE EMERGENCY ACCESS TO ELEVATORS:
 (A) FOR EACH BUILDING IN THIS STATE WHICH IS SIX OR
 MORE STORIES IN HEIGHT, INCLUDING, BUT NOT LIMITED TO,
 HOTELS AND CONDOMINIUMS, ON WHICH A BUILDING PERMIT IS
 ISSUED AFTER SEPTEMBER 30, 2006, ALL OF THE KEYS FOR
 ELEVATORS THAT ALLOW PUBLIC ACCESS, INCLUDING, BUT NOT
 LIMITED TO, SERVICE AND FREIGHT ELEVATORS, MUST BE
 KEYED SO AS TO ALLOW ALL ELEVATORS WITHIN EACH OF THE
 SEVEN STATE EMERGENCY RESPONSE REGIONS TO OPERATE IN
 FIRE EMERGENCY SITUATIONS WITH ONE MASTER ELEVATOR KEY.
  
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT
 AND COMPLIANCE.
  
  
  
  
 NEW COMMENT:
  
  
 1) PLEASE CLARIFY THE 4 HR FIRE RATING INDICATED FOR
 THE ELEVATOR AND STAIRWELL SHAFTS ON THE LIFE SAFETY
 SHEETS 1- 3, AND THE CALLOUT LISTING ON LS 4 INDICATING
 2 HR.
  
 WHICH IS CORRECT AND CORRECT.
  
  
  
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  