Plan Review Notes
Plan Review Notes For Permit 18050056
Permit Number 18050056
Review Stop B
Sequence Number 3
Notes
Date Text
2019-05-13 11:10:59PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED. THE PLANS HAVE SEVERAL REFERENCES TO THE
 FBC SIXTH EDITION (2017) WHICH WENT INTO EFFECT ON
 JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR ON OR
 AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC SIXTH EDITION (2017). THE FOUNDATION
 PERMIT FOR THIS PROJECT (#17111142) WAS APPLIED FOR ON
 11/30/2017, THEREFORE THIS PROJECT IS UNDER THE FBC
 FIFTH EDITION (2014). REVISE PLANS TO ONLY REFERENCE
 THE FBC FIFTH EDITION (2014) FS CHAPTER 553
  
 2) COMPLIED. SPECIFY THE TYPE OF OCCUPANCY AND
 CONSTRUCTION TYPE FOR THE BUILDING ON THE PLANS. FBC
 302.1 AND 602.1
  
 3) NOT ADDRESSED. A PRE-CONSTRUCTION ELEVATION
 CERTIFICATE IS REQUIRED TO BE SUBMITTED. THIS PROJECT
 IS LOCATED IN A SPECIAL FLOOD HAZARD AREA. THE FLOOD
 ZONE IS AE THE BASE FLOOD ELEVATION FOR THE BUILDING IS
 7' NAVD 88 PLUS THE 2' FREEBOARD REQUIRED BY THE CITY
 OF WEST PALM BEACH'S FLOOD ORDINANCE. THE LOWEST FLOOR
 OF THE BUILDING AND THE EQUIPMENT SERVICING THE
 BUILDING IS REQUIRED TO BE AT OR ABOVE 9'-0" NAVD 88.
 ELEVATION CERTIFICATES FROM A FLORIDA LICENSED SURVEYOR
 WILL BE REQUIRED AT VARIOUS STAGES OF CONSTRUCTION. A
 PRE-CONSTRUCTION ELEVATION CERTIFICATED BASED ON THE
 PROPOSED PLANS IS REQUIRED AT THIS TIME.
  
 4) COMPLIED. THERE ARE SEVERAL NOTES ON THE PLAN THAT
 CITE THE FBC RESIDENTIAL, THESE NOTES DO NOT APPLY TO
 THIS PROJECT. THIS BUILDING CONTAINS MULTIPLE
 RESIDENTIAL UNITS THAT ARE SPECIFIED AS CONDOMINIUMS
 AND AS SUCH ARE CONSIDERED R-2 OCCUPANCY TYPES AND ARE
 SUBJECT TO THE FBC BUILDING SCOPING REQUIREMENTS. FBC
 101.2
  
 5) PARTIALLY COMPLIED. THE CODE SECTION FOR GUARD
 HEIGHT IS INCORRECTLY SPECIFIED AS FBC 1015.3 ON THE
 PLANS. REVISE THE STAIR INFORMATION ON SHEET A201 TO
 2014 FBC SECTION 1607.8 FOR LOADS AND SECTION 1013.3
 FOR REQUIRED 42" GUARD HEIGHT, EXCEPT WITHIN INDIVIDUAL
 DWELLING UNITS OF R-2 OCCUPANCIES.
  
 6) PARTIALLY COMPLIED. THE CODE SECTION FOR THE GUARD
 OPENINGS IS INCORRECTLY SPECIFIED AS FBC 1015.4 ON THE
 PLANS. SHOW COMPLIANCE WITH FBC 1013.4 FOR GUARD
 OPENING LIMITATIONS.
  
 7) NOT ADDRESSED. A SCHEMATIC FIRE SPRINKLER PLAN IS
 REQUIRED TO BE SUBMITTED BY FBC 107.3.5.1. PROVIDE A
 FIRE SPRINKLER PLAN. FBC 903.2.11.3 ( SEE FIRE REVIEW
 COMMENTS)
  
 8) PARTIALLY COMPLIED. THE LIFE SAFETY PLAN THAT WAS
 SUBMITTED HAS SOME ERRORS AND OMISSIONS. SHEET LS-1
 SHOWS THE EGRESS PATH OF TRAVEL FROM THE FIRE PUMP ROOM
 THROUGH WALLS AND THE ADJACENT UNIT. INDICATE THE FIRE
 RATED WALLS AT THE SHAFTS, ELEVATOR HOISTWAY, EXIT
 STAIRWAYS, ETC. ON THE LIFE SAFETY FLOOR PLANS BY USING
 DIFFERENT COMBINATIONS OF DOTS AND DASHES ALONG WITH A
 CORRESPONDING SCHEDULE. SHOW THE OVERALL DIAGONAL
 DISTANCE OF THE AREA SERVED AND THE EXIT STAIR
 SEPARATION DISTANCE ON THE LIFE SAFETY FLOOR PLANS.
 SHOW THE OCCUPANT LOADS FOR EACH AREA ON THE LS FLOOR
 PLANS. SHOW THE EGRESS DOOR SIZES AND OCCUPANT CAPACITY
 ON THE LS FLOOR PLANS. THE EXIT ACCESS TRAVEL DISTANCE
 IS MEASURED FROM THE MOST REMOTE POINT WITHIN A STORY
 TO AN EXIT AND INCLUDES THE COMMON PATH OF TRAVEL PER
 2014 FBC 1016.3. THE MOST REMOTE POINT ON THE BALCONIES
 NEEDS TO BE INCLUDED IN THE TRAVEL DISTANCE. PLEASE PUT
 THE TRAVEL DISTANCES ON THE TRAVEL PATHS SHOWN ON THE
 LS FLOOR PLANS. THE FIRE RATINGS OF THE DOORS ARE NOT
 SPECIFIED IN THE DOOR SCHEDULE. PROVIDE A LIFE SAFETY
 PLAN, SHOWING OCCUPANT LOADS, TRAVEL DISTANCES, ETC.
 FBC 1001.4 ( SEE FIRE REVIEW COMMENTS)
  
 9) NOT ADDRESSED. THE EQUIPMENT IS NOT SHOWN ON THE
 PLANS. SHOW COMPLIANCE WITH FBC 901.8. FIRE PUMP AND
 AUTOMATIC SPRINKLER SYSTEM RISER ROOMS SHALL BE
 DESIGNED WITH ADEQUATE SPACE FOR ALL EQUIPMENT
 NECESSARY FOR THE INSTALLATION, AS DEFINED BY THE
 MANUFACTURER, WITH SUFFICIENT WORKING ROOM AROUND THE
 STATIONARY EQUIPMENT. CLEARANCES AROUND EQUIPMENT TO
 ELEMENTS OF PERMANENT CONSTRUCTION, INCLUDING OTHER
 INSTALLED EQUIPMENT AND APPLIANCES, SHALL BE SUFFICIENT
 TO ALLOW INSPECTION, SERVICE, REPAIR OR REPLACEMENT
 WITHOUT REMOVING SUCH ELEMENTS OF PERMANENT
 CONSTRUCTION OR DISABLING THE FUNCTION OF A REQUIRED
 FIRE-RESISTANCE-RATED ASSEMBLY. FIRE PUMP AND AUTOMATIC
 SPRINKLER SYSTEM RISER ROOMS SHALL BE PROVIDED WITH A
 DOOR(S) AND UNOBSTRUCTED PASSAGEWAY LARGE ENOUGH TO
 ALLOW REMOVAL OF THE LARGEST PIECE OF EQUIPMENT.
  
 10) COMPLIED.
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) PARTIALLY COMPLIED. THE BATHROOM ON THE GROUND
 FLOOR IS REQUIRED TO BE A SPECIFICATION B BATHROOM. THE
 2'-8" DOOR (D11) AT THE GROUND FLOOR BATHROOM DOES NOT
 PROVIDE A 32" NOMINAL CLEAR OPENING AS REQUIRED BY FAIR
 HOUSING FOR A USABLE BATHROOM. THERE IS NO DOOR ID TAG
 FOR THE POCKET DOOR AT THE GROUND FLOOR BATHROOM. THE
 POCKET DOOR AT THE STUDY BATHROOM IS MISTAKENLY TAGGED
 D3, WHICH IS A 2'-8" LOUVERED DOOR. THE GLASS WALL AND
 DOOR AT THE SPEC. B BATHROOM IS NOT ALLOWED TO BE IN
 THE CLEAR FLOOR SPACE FOR THE TOILET. SPECIFY THE
 REQUIRED DIMENSIONS AT THE CLEAR FLOOR SPACE AREAS ON
 THE ACCESSIBLE ROUTE FLOOR PLANS. NOTE: THIS PROJECT IS
 FOR A PRIVATE MULTI-FAMILY RESIDENCE AND NO FEDERAL
 FUNDING IS BEING USED, THEREFORE IT IS NOT REQUIRED TO
 COMPLY WITH THE ADA, HOWEVER, IT IS REQUIRED TO COMPLY
 WITH FAIR HOUSING. SHOW COMPLIANCE WITH FAIR HOUSING
 REQUIREMENTS FOR SCHEDULE A OR B BATHROOM REQUIREMENTS
 AS SPECIFIED IN THE FAIR HOUSING ACT DESIGN MANUAL. FBC
 ACCESSIBILITY - FAIR HOUSING GUIDELINES (SEE PLUMBING
 REVIEW COMMENTS.)
  
 14) COMPLIED.
  
 15) NOT ADDRESSED. THE ACTUAL TEST REPORTS FOR THE
 SOUND PROOFING MATERIALS ARE REQUIRED TO BE SUBMITTED
 FOR REVIEW. THESE DOCUMENTS CAN BE DEFERRED IF LISTED
 IF LISTED IN THE CONSTRUCTION DOCUMENTS. SEE COMMENT
 #16. SHOW COMPLIANCE WITH THE FOLLOWING: FBC 1207.2
 AIR-BORNE SOUND. WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS FROM EACH OTHER OR
 FROM PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 IF
 FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN
 CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES;
 RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED,
 INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING
 UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 TESTING REPORTS FOR SOUND PROOFING INSULATION FOR TILE
 FLOORING OR OTHER HARD SURFACE FLOORING MATERIAL IS
 REQUIRED TO BE SUBMITTED. THIS CAN BE A DEFERRED
 SUBMITTAL.
  
 16) NOT ADDRESSED. FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT ROOFING MATERIALS,
 WINDOW/GLASS TYPES, STRUCTURAL MULLIONS, ROOF HATCHES
 AND EXTERIOR DOOR TYPES. YOU MAY REQUEST THAT THESE
 ITEMS BE DEFERRED TO A LATER DATE. SEE BELOW.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 17) PARTIALLY ADDRESSED. THERE IS A PORTION OF THE
 PARAPET WALL LOCATED WITHIN 10 FEET OF THE ROOF HATCH
 THAT IS ONLY 24" ABOVE THE ROOF DECK. SEE SHEETS A701
 AND A403. THE ROOF HATCH SHOWN ON THE PLANS DOES NOT
 COMPLY WITH THE REQUIREMENTS FOR SIZE AND GUARDS. ON
 SHEET A502 THE STAIR SECTIONS ARE NOT IDENTIFIED AS
 STAIR #1 AND STAIR #2. THERE IS A DOOR SHOWN AT THE
 GROUND LEVEL ON THE SECTION FOR STAIR #1, WHERE THERE
 IS NO DOOR SHOWN ON THE FLOOR PLANS. SEE A502 AND A503.
 THE HANDRAILS FOR THE EXIT STAIRS DO NOT HAVE
 EXTENSIONS AT THE TOP AND BOTTOM AS REQUIRED BY FAIR
 HOUSING AND ANSI117.1. THE HANDRAIL IS REQUIRED TO
 EXTEND HORIZONTALLY AT THE TOP FOR 12" AND FOLLOW THE
 SLOPE OF THE STAIRS FOR A DISTANCE OF AT LEAST ONE
 TREAD DEPTH. SOME OF THE STAIRS SHOWN ON SHEET1009.16
 STAIRWAY TO ROOF. IN BUILDINGS FOUR OR MORE STORIES
 ABOVE GRADE PLANE, ONE STAIRWAY SHALL EXTEND TO THE
 ROOF SURFACE, UNLESS THE ROOF HAS A SLOPE STEEPER THAN
 FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT
 SLOPE). IN BUILDINGS WITHOUT AN OCCUPIED ROOF, ACCESS
 TO THE ROOF FROM THE TOP STORY SHALL BE PERMITTED TO BE
 BY AN ALTERNATING TREAD DEVICE.
 1009.16.1 ROOF ACCESS. WHERE A STAIRWAY IS PROVIDED TO
 A ROOF, ACCESS TO THE ROOF SHALL BE PROVIDED THROUGH A
 PENTHOUSE COMPLYING WITH SECTION 1509.2.
 EXCEPTION: IN BUILDINGS WITHOUT AN OCCUPIED ROOF,
 ACCESS TO THE ROOF SHALL BE PERMITTED TO BE A ROOF
 HATCH OR TRAP DOOR NOT LESS THAN 16 SQUARE FEET (1.5
 M2) IN AREA AND HAVING A MINIMUM DIMENSION OF 2 FEET
 (610 MM).
 1009.16.2 PROTECTION AT ROOF HATCH OPENINGS. WHERE THE
 ROOF HATCH OPENING PROVIDING THE REQUIRED ACCESS IS
 LOCATED WITHIN 10 FEET (3049 MM) OF THE ROOF EDGE, SUCH
 ROOF ACCESS OR ROOF EDGE SHALL BE PROTECTED BY GUARDS
 INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF SECTION
 1013.
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20) COMPLIED.
  
 21) COMPLIED.
  
 22) COMPLIED.
  
 23) COMPLIED.
  
 24) PARTIALLY COMPLIED. THE BUILDING CODE ANALYSIS ON
 LS-1 HAS A 4 HOUR FIRE RATING FOR THE STAIRS AND
 ELEVATOR SHAFT. SHEET LS-4 HAS A 2 HOUR RATING IN
 DETAIL 10. SHOW COMPLIANCE WITH FBC 3002.1 HOISTWAY
 ENCLOSURE PROTECTION. ELEVATOR, DUMBWAITER AND OTHER
 HOISTWAY ENCLOSURES SHALL BE SHAFT ENCLOSURES COMPLYING
 WITH SECTION 713. FBC 713.4 FIRE-RESISTANCE RATING.
 SHAFT ENCLOSURES SHALL HAVE A FIRE-RESISTANCE RATING OF
 NOT LESS THAN 2 HOURS WHERE CONNECTING FOUR STORIES OR
 MORE, AND NOT LESS THAN 1 HOUR WHERE CONNECTING LESS
 THAN FOUR STORIES. THE NUMBER OF STORIES CONNECTED BY
 THE SHAFT ENCLOSURE SHALL INCLUDE ANY BASEMENTS BUT NOT
 ANY MEZZANINES. SHAFT ENCLOSURES SHALL HAVE A
 FIRE-RESISTANCE RATING NOT LESS THAN THE FLOOR ASSEMBLY
 PENETRATED, BUT NEED NOT EXCEED 2 HOURS. SHAFT
 ENCLOSURES SHALL MEET THE REQUIREMENTS OF SECTION
 703.2.1.
  
 25) COMPLIED.
  
 26) COMPLIED.
  
 27) COMPLIED.
  
 28) SEE COMMENTS FOR ITEM #8. IDENTIFY THE FIRE RATED
 WALLS ON THE PLANS. FBC 107.2.1
  
 29) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  
  
  
  