| 2019-04-11 10:53:12 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. SMOKE ALARMS MUST BE INSTALLED AT LEAST THREE FEET |
| | FROM BATHROOM DOOR, THREE FEET FROM CEILING FANS, AND |
| | THREE FEET FROM ANY MECHANICAL DUCT. PROVIDE |
| | CORRECTIONS. NFPA 72:29.8.3.4 (FIRST FLLOR STILL SHOWS |
| | SMOKE ALARMS TOO CLOSE TO BATHROOM AND TO FAN IN GUEST |
| | BEDROOM.) |
| | 5. CORRECTED. |
| | 7. ALL RECEPTACLE OUTLETS IN LAUNDRY REQUIRE GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8 (COMMENT |
| | STATES "ALL" RECEPTACLES IN LAUNDRY. SOME HAVE NOT BEEN |
| | CORRECTED TO GFCI PROTECTED.) |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | 10. CORRECTED. |
| | 11. CORRECTED. |
| | 12. CORRECTED. |
| | 13. CORRECTED. |
| | 14. CORRECTED. |
| | 15. CORRECTED. |
| | 16. CORRECTED. |
| | 17. CORRECTED. |
| | 18. CORRECTED. |
| | |
| | NEW COMMENTS: |
| | |
| | 19. WALK IN CLOSETS SHOW A RECEPTACLE "ABOVE CEILING". |
| | PROVIDE CLARIFICATION. HOW WILL THIS RECEPTACLE BE |
| | ACCESSED IF IT IS ABOVE THE CEILING? WHAT IS PURPOSE OF |
| | THIS RECEPTACLE? WPB FBC 107.2.1 |
| | 20. REVISED RISER DIAGRAM SHOWS THE JOCKEY PUMP IN THE |
| | FIRE PUMP ROOM BEING FED FROM THE FIRE PUMP CONTROLLER. |
| | THIS IS NOT PERMITTED PER CODE. PROVIDE CORRECTION. NEC |
| | 695.6(E), 695.6(I)(6) |
| | 21. FEED FROM THE 200 AMP METER TO THE FIRE PUMP |
| | CONTROLLER SHOULD NOT INCLUDE AND EQUIPMENT GROUNDING |
| | CONDUCTOR. HOWEVER, THIS SERVICE SHOULD BE TIED TO THE |
| | GROUNDING ELECTRODE SYSTEM. PROVIDE CORRECTION. NEC |
| | 250.6, 250.50 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |