Plan Review Notes
Plan Review Notes For Permit 18050056
Permit Number 18050056
Review Stop E
Sequence Number 2
Notes
Date Text
2019-04-11 10:53:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. SMOKE ALARMS MUST BE INSTALLED AT LEAST THREE FEET
 FROM BATHROOM DOOR, THREE FEET FROM CEILING FANS, AND
 THREE FEET FROM ANY MECHANICAL DUCT. PROVIDE
 CORRECTIONS. NFPA 72:29.8.3.4 (FIRST FLLOR STILL SHOWS
 SMOKE ALARMS TOO CLOSE TO BATHROOM AND TO FAN IN GUEST
 BEDROOM.)
 5. CORRECTED.
 7. ALL RECEPTACLE OUTLETS IN LAUNDRY REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8 (COMMENT
 STATES "ALL" RECEPTACLES IN LAUNDRY. SOME HAVE NOT BEEN
 CORRECTED TO GFCI PROTECTED.)
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
 16. CORRECTED.
 17. CORRECTED.
 18. CORRECTED.
  
 NEW COMMENTS:
  
 19. WALK IN CLOSETS SHOW A RECEPTACLE "ABOVE CEILING".
 PROVIDE CLARIFICATION. HOW WILL THIS RECEPTACLE BE
 ACCESSED IF IT IS ABOVE THE CEILING? WHAT IS PURPOSE OF
 THIS RECEPTACLE? WPB FBC 107.2.1
 20. REVISED RISER DIAGRAM SHOWS THE JOCKEY PUMP IN THE
 FIRE PUMP ROOM BEING FED FROM THE FIRE PUMP CONTROLLER.
 THIS IS NOT PERMITTED PER CODE. PROVIDE CORRECTION. NEC
 695.6(E), 695.6(I)(6)
 21. FEED FROM THE 200 AMP METER TO THE FIRE PUMP
 CONTROLLER SHOULD NOT INCLUDE AND EQUIPMENT GROUNDING
 CONDUCTOR. HOWEVER, THIS SERVICE SHOULD BE TIED TO THE
 GROUNDING ELECTRODE SYSTEM. PROVIDE CORRECTION. NEC
 250.6, 250.50
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER