| 2019-03-28 18:45:33 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING (COMMENTS FROM THE FIRST REVIEW HAVE |
| | NOT BEEN ADDRESSED.) |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PLANS HAVE SEVERAL REFERENCES TO THE FBC SIXTH |
| | EDITION (2017) WHICH WENT INTO EFFECT ON JANUARY 1, |
| | 2018. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT DATE |
| | ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC SIXTH |
| | EDITION (2017). THE FOUNDATION PERMIT FOR THIS PROJECT |
| | (#17111142) WAS APPLIED FOR ON 11/30/2017, THEREFORE |
| | THIS PROJECT IS UNDER THE FBC FIFTH EDITION (2014). |
| | REVISE PLANS TO ONLY REFERENCE THE FBC FIFTH EDITION |
| | (2014) FS CHAPTER 553 |
| | |
| | 2) SPECIFY THE TYPE OF OCCUPANCY AND CONSTRUCTION TYPE |
| | FOR THE BUILDING ON THE PLANS. FBC 302.1 AND 602.1 |
| | |
| | 3) THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD |
| | AREA. THE FLOOD ZONE IS AE THE BASE FLOOD ELEVATION FOR |
| | THE BUILDING IS 7' NAVD 88 PLUS THE 2' FREEBOARD |
| | REQUIRED BY THE CITY OF WEST PALM BEACH'S FLOOD |
| | ORDINANCE. THE LOWEST FLOOR OF THE BUILDING AND THE |
| | EQUIPMENT SERVICING THE BUILDING IS REQUIRED TO BE AT |
| | OR ABOVE 9'-0" NAVD 88. ELEVATION CERTIFICATES FROM A |
| | FLORIDA LICENSED SURVEYOR WILL BE REQUIRED AT VARIOUS |
| | STAGES OF CONSTRUCTION. A PRE-CONSTRUCTION ELEVATION |
| | CERTIFICATED BASED ON THE PROPOSED PLANS IS REQUIRED AT |
| | THIS TIME. |
| | |
| | 4) THERE ARE SEVERAL NOTES ON THE PLAN THAT CITE THE |
| | FBC RESIDENTIAL, THESE NOTES DO NOT APPLY TO THIS |
| | PROJECT. THIS BUILDING CONTAINS MULTIPLE RESIDENTIAL |
| | UNITS THAT ARE SPECIFIED AS CONDOMINIUMS AND AS SUCH |
| | ARE CONSIDERED R-2 OCCUPANCY TYPES AND ARE SUBJECT TO |
| | THE FBC BUILDING SCOPING REQUIREMENTS. FBC 101.2 |
| | |
| | 5) REVISE THE STAIR INFORMATION ON SHEET A201 TO 2014 |
| | FBC SECTION 1607.8 FOR LOADS AND SECTION 1013.3 FOR |
| | REQUIRED 42" GUARD HEIGHT, EXCEPT WITHIN INDIVIDUAL |
| | DWELLING UNITS OF R-2 OCCUPANCIES. |
| | |
| | 6) SHOW COMPLIANCE WITH FBC 1013.4 FOR GUARD OPENING |
| | LIMITATIONS. |
| | |
| | 7) PROVIDE A FIRE SPRINKLER PLAN. FBC 903.2.11.3 ( SEE |
| | FIRE REVIEW COMMENTS) |
| | |
| | 8) PROVIDE A LIFE SAFETY PLAN, SHOWING OCCUPANT LOADS, |
| | TRAVEL DISTANCES, ETC. FBC 1001.4 ( SEE FIRE REVIEW |
| | COMMENTS) |
| | |
| | 9) SHOW COMPLIANCE WITH FBC 901.8. FIRE PUMP AND |
| | AUTOMATIC SPRINKLER SYSTEM RISER ROOMS SHALL BE |
| | DESIGNED WITH ADEQUATE SPACE FOR ALL EQUIPMENT |
| | NECESSARY FOR THE INSTALLATION, AS DEFINED BY THE |
| | MANUFACTURER, WITH SUFFICIENT WORKING ROOM AROUND THE |
| | STATIONARY EQUIPMENT. CLEARANCES AROUND EQUIPMENT TO |
| | ELEMENTS OF PERMANENT CONSTRUCTION, INCLUDING OTHER |
| | INSTALLED EQUIPMENT AND APPLIANCES, SHALL BE SUFFICIENT |
| | TO ALLOW INSPECTION, SERVICE, REPAIR OR REPLACEMENT |
| | WITHOUT REMOVING SUCH ELEMENTS OF PERMANENT |
| | CONSTRUCTION OR DISABLING THE FUNCTION OF A REQUIRED |
| | FIRE-RESISTANCE-RATED ASSEMBLY. FIRE PUMP AND AUTOMATIC |
| | SPRINKLER SYSTEM RISER ROOMS SHALL BE PROVIDED WITH A |
| | DOOR(S) AND UNOBSTRUCTED PASSAGEWAY LARGE ENOUGH TO |
| | ALLOW REMOVAL OF THE LARGEST PIECE OF EQUIPMENT. |
| | |
| | 10) THERE IS A CONFLICT IN THE FINISH FLOOR ELEVATIONS |
| | BETWEEN SHEET C-1 AND SHEET A201. SHEET C-1 HAS THE |
| | ELEVATIONS IN NAVD 88 AND A201 IS IN NGVD 29. ALL OF |
| | THE ELEVATIONS ARE TO USE THE CURRENT VERTICAL DATA |
| | USED BY FEMA, WHICH IS NAVD 88. |
| | |
| | 11) ON SHEET A207, THE FLOOR PLAN FOR THE SEVENTH FLOOR |
| | IS INCORRECTLY LABELED AS THE SECOND FLOOR. FBC 107.2.1 |
| | |
| | 12) ON SHEET A301 THE GROUND FLOOR CEILING PLAN DOES |
| | NOT SHOW THE OPENING FOR THE STAIRWAY TO THE SECOND |
| | FLOOR. FBC 107.2.1 |
| | |
| | 13) NOTE: THIS PROJECT IS FOR A PRIVATE MULTI-FAMILY |
| | RESIDENCE AND NO FEDERAL FUNDING IS BEING USED, |
| | THEREFORE IT IS NOT REQUIRED TO COMPLY WITH THE ADA, |
| | HOWEVER, IT IS REQUIRED TO COMPLY WITH FAIR HOUSING. |
| | SHOW COMPLIANCE WITH FAIR HOUSING REQUIREMENTS FOR |
| | SCHEDULE A OR B BATHROOM REQUIREMENTS AS SPECIFIED IN |
| | THE FAIR HOUSING ACT DESIGN MANUAL. FBC ACCESSIBILITY - |
| | FAIR HOUSING GUIDELINES (SEE PLUMBING REVIEW COMMENTS.) |
| | |
| | 14) THE COMPONENT AND CLADDING PRESSURES FOR THE |
| | EXTERIOR DOORS AND WINDOWS HAVE NOT BEEN PROVIDED IN |
| | THE SCHEDULES ON SHEET A601. THE STRUCTURAL SHEETS HAVE |
| | BEEN REMOVED AND ARE UNDER ANOTHER PERMIT. FBC 107.2.1 |
| | |
| | 15) SHOW COMPLIANCE WITH THE FOLLOWING: FBC 1207.2 |
| | AIR-BORNE SOUND. WALLS, PARTITIONS AND FLOOR/CEILING |
| | ASSEMBLIES SEPARATING DWELLING UNITS FROM EACH OTHER OR |
| | FROM PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND |
| | TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 IF |
| | FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN |
| | CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; |
| | RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING, |
| | VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED, |
| | INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED |
| | RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING |
| | UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | TESTING REPORTS FOR SOUND PROOFING INSULATION FOR TILE |
| | FLOORING OR OTHER HARD SURFACE FLOORING MATERIAL IS |
| | REQUIRED TO BE SUBMITTED. THIS CAN BE A DEFERRED |
| | SUBMITTAL. |
| | |
| | 16) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL |
| | MULLIONS, ROOF HATCHES AND EXTERIOR DOOR TYPES. YOU MAY |
| | REQUEST THAT THESE ITEMS BE DEFERRED TO A LATER DATE. |
| | SEE BELOW. |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 17) THE ROOF HATCH SHOWN ON THE PLANS DOES NOT COMPLY |
| | WITH THE REQUIREMENTS FOR SIZE AND GUARDS. 1009.16 |
| | STAIRWAY TO ROOF. IN BUILDINGS FOUR OR MORE STORIES |
| | ABOVE GRADE PLANE, ONE STAIRWAY SHALL EXTEND TO THE |
| | ROOF SURFACE, UNLESS THE ROOF HAS A SLOPE STEEPER THAN |
| | FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT |
| | SLOPE). IN BUILDINGS WITHOUT AN OCCUPIED ROOF, ACCESS |
| | TO THE ROOF FROM THE TOP STORY SHALL BE PERMITTED TO BE |
| | BY AN ALTERNATING TREAD DEVICE. |
| | 1009.16.1 ROOF ACCESS. WHERE A STAIRWAY IS PROVIDED TO |
| | A ROOF, ACCESS TO THE ROOF SHALL BE PROVIDED THROUGH A |
| | PENTHOUSE COMPLYING WITH SECTION 1509.2. |
| | EXCEPTION: IN BUILDINGS WITHOUT AN OCCUPIED ROOF, |
| | ACCESS TO THE ROOF SHALL BE PERMITTED TO BE A ROOF |
| | HATCH OR TRAP DOOR NOT LESS THAN 16 SQUARE FEET (1.5 |
| | M2) IN AREA AND HAVING A MINIMUM DIMENSION OF 2 FEET |
| | (610 MM). |
| | 1009.16.2 PROTECTION AT ROOF HATCH OPENINGS. WHERE THE |
| | ROOF HATCH OPENING PROVIDING THE REQUIRED ACCESS IS |
| | LOCATED WITHIN 10 FEET (3049 MM) OF THE ROOF EDGE, SUCH |
| | ROOF ACCESS OR ROOF EDGE SHALL BE PROTECTED BY GUARDS |
| | INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF SECTION |
| | 1013. |
| | |
| | 18) ON SHEET A602, #4 THE ENLARGED STAIR PLAN FOR THE |
| | SEVENTH FLOOR, THE ELEVATOR EQUIPMENT IS NOT LABELED |
| | AND SOME OF THE DIMENSIONS OF THE ROOM AND IT'S STAIR |
| | LANDING ARE MISSING. FBC 107.2.1 |
| | |
| | 19) THE STAIR PLANS ON SHEET A602 HAVE ARE SPECIFIED AS |
| | BEING 1/4" SCALE AND THEY ARE ACTUALLY 3/8" SCALE. FBC |
| | 107.2.1 |
| | |
| | 20) THE PLANS SHOW A SHIPS LADDER FOR ACCESS TO THE |
| | ELEVATOR EQUIPMENT ROOM. THE ROOM FOR ELEVATOR |
| | EQUIPMENT THAT MUST BE ACCESSED FOR MAINTENANCE IS |
| | REQUIRED TO BE ACCESSED BY A STAIRWAY. FBC 1009.17 |
| | |
| | 21) SHOW COMPLIANCE WITH FBC 1009.3.1.4 OPENINGS. |
| | OPENINGS IN AN EXIT ACCESS STAIRWAY ENCLOSURE SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 716 AS REQUIRED |
| | FOR FIRE BARRIERS. DOORS SHALL BE SELF- OR |
| | AUTOMATIC-CLOSING BY SMOKE DETECTION IN ACCORDANCE WITH |
| | SECTION 716.5.9.3. |
| | 1009.3.1.4.1 PROHIBITED OPENINGS. OPENINGS OTHER THAN |
| | THOSE NECESSARY FOR THE PURPOSE OF THE EXIT ACCESS |
| | STAIRWAY ENCLOSURE SHALL NOT BE PERMITTED IN EXIT |
| | ACCESS STAIRWAY ENCLOSURES. THE ELEVATOR EQUIPMENT ROOM |
| | IS NOT ALLOWED TO OPEN INTO THE EXIT ACCESS STAIRWAY AS |
| | SHOWN ON THE PLANS. |
| | |
| | 22) SHOW COMPLIANCE WITH FBC 1009.3.1.2 FIRE-RESISTANCE |
| | RATING. EXIT ACCESS STAIRWAY ENCLOSURES SHALL HAVE A |
| | FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS WHERE |
| | CONNECTING FOUR STORIES OR MORE. |
| | |
| | 23) SHOW COMPLIANCE WITH FBC 1022.5 PENETRATIONS. |
| | PENETRATIONS INTO AND OPENINGS THROUGH INTERIOR EXIT |
| | STAIRWAYS AND RAMPS ARE PROHIBITED EXCEPT FOR REQUIRED |
| | EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR |
| | INDEPENDENT VENTILATION OR PRESSURIZATION, SPRINKLER |
| | PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR FIRE |
| | DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY |
| | SERVING THE INTERIOR EXIT STAIRWAY AND RAMP AND |
| | TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE |
| | INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE PROTECTED |
| | IN ACCORDANCE WITH SECTION 714. THERE SHALL BE NO |
| | PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER |
| | PROTECTED OR NOT, BETWEEN ADJACENT INTERIOR EXIT |
| | STAIRWAYS AND RAMPS. |
| | |
| | 24) SHOW COMPLIANCE WITH FBC 3002.1 HOISTWAY ENCLOSURE |
| | PROTECTION. ELEVATOR, DUMBWAITER AND OTHER HOISTWAY |
| | ENCLOSURES SHALL BE SHAFT ENCLOSURES COMPLYING WITH |
| | SECTION 713. FBC 713.4 FIRE-RESISTANCE RATING. SHAFT |
| | ENCLOSURES SHALL HAVE A FIRE-RESISTANCE RATING OF NOT |
| | LESS THAN 2 HOURS WHERE CONNECTING FOUR STORIES OR |
| | MORE, AND NOT LESS THAN 1 HOUR WHERE CONNECTING LESS |
| | THAN FOUR STORIES. THE NUMBER OF STORIES CONNECTED BY |
| | THE SHAFT ENCLOSURE SHALL INCLUDE ANY BASEMENTS BUT NOT |
| | ANY MEZZANINES. SHAFT ENCLOSURES SHALL HAVE A |
| | FIRE-RESISTANCE RATING NOT LESS THAN THE FLOOR ASSEMBLY |
| | PENETRATED, BUT NEED NOT EXCEED 2 HOURS. SHAFT |
| | ENCLOSURES SHALL MEET THE REQUIREMENTS OF SECTION |
| | 703.2.1. |
| | |
| | 25) SHOW COMPLIANCE WITH FBC 3002.4 ELEVATOR CAR TO |
| | ACCOMMODATE AMBULANCE STRETCHER. ANY BUILDING THAT IS |
| | MORE THAN THREE STORIES HIGH OR IN WHICH THE VERTICAL |
| | DISTANCE BETWEEN THE BOTTOM TERMINAL LANDING AND THE |
| | TOP TERMINAL LANDING EXCEEDS 25 FEET (7620 MM), MUST BE |
| | CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER ELEVATOR |
| | THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE |
| | DEPARTMENT EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR |
| | CAR SHALL BE OF SUCH A SIZE AND ARRANGEMENT TO |
| | ACCOMMODATE AN AMBULANCE STRETCHER 24 INCHES BY 76 |
| | INCHES (610 MM BY 2134 MM) WITH NOT LESS THAN 5-INCH |
| | (127 MM) RADIUS CORNERS, IN THE HORIZONTAL, OPEN |
| | POSITION AND SHALL BE IDENTIFIED BY THE INTERNATIONAL |
| | SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE). |
| | THE SYMBOL SHALL NOT BE LESS THAN 3 INCHES (76 MM) IN |
| | HEIGHT AND SHALL BE PLACED INSIDE ON BOTH SIDES OF THE |
| | HOISTWAY DOOR FRAME. |
| | |
| | 26) 3006.4 MACHINE ROOMS AND MACHINERY SPACES. ELEVATOR |
| | MACHINE ROOMS AND MACHINERY SPACES SHALL BE ENCLOSED |
| | WITH FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 711, OR BOTH. THE |
| | FIRE-RESISTANCE RATING SHALL BE NOT LESS THAN THE |
| | REQUIRED RATING OF THE HOISTWAY ENCLOSURE SERVED BY THE |
| | MACHINERY. OPENINGS IN THE FIRE BARRIERS SHALL BE |
| | PROTECTED WITH ASSEMBLIES HAVING A FIRE PROTECTION |
| | RATING NOT LESS THAN THAT REQUIRED FOR THE HOISTWAY |
| | ENCLOSURE DOORS. |
| | EXCEPTIONS: 1. WHERE MACHINE ROOMS AND MACHINERY SPACES |
| | DO NOT ABUT AND HAVE NO OPENINGS TO THE HOISTWAY |
| | ENCLOSURE THEY SERVE THE FIRE BARRIERS CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES |
| | CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH, |
| | SHALL BE PERMITTED TO BE REDUCED TO A 1-HOUR |
| | FIRE-RESISTANCE RATING. |
| | |
| | 27) F] 913.2 PROTECTION AGAINST INTERRUPTION OF |
| | SERVICE. THE FIRE PUMP, DRIVER AND CONTROLLER SHALL BE |
| | PROTECTED IN ACCORDANCE WITH NFPA 20 AGAINST POSSIBLE |
| | INTERRUPTION OF SERVICE THROUGH DAMAGE CAUSED BY |
| | EXPLOSION, FIRE, FLOOD, EARTHQUAKE, RODENTS, INSECTS, |
| | WINDSTORM, FREEZING, VANDALISM AND OTHER ADVERSE |
| | CONDITIONS. |
| | 913.2.1 PROTECTION OF FIRE PUMP ROOMS. FIRE PUMPS SHALL |
| | BE LOCATED IN ROOMS THAT ARE SEPARATED FROM ALL OTHER |
| | AREAS OF THE BUILDING BY 2-HOUR FIRE BARRIERS |
| | CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR 2-HOUR |
| | HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 711, OR BOTH. |
| | EXCEPTIONS: |
| | 1. IN OTHER THAN HIGH-RISE BUILDINGS, SEPARATION BY |
| | 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 707 OR 1-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED |
| | IN ACCORDANCE WITH SECTION 711, OR BOTH, SHALL BE |
| | PERMITTED IN BUILDINGS EQUIPPED THROUGHOUT WITH AN |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 903.3.1.1 OR 903.3.1.2. |
| | |
| | 2. SEPARATION IS NOT REQUIRED FOR FIRE PUMPS PHYSICALLY |
| | SEPARATED IN ACCORDANCE WITH NFPA 20. |
| | |
| | 28) IDENTIFY THE FIRE RATED WALLS ON THE PLANS. FBC |
| | 107.2.1 |
| | |
| | 29) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |