| 2018-06-06 16:47:20 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18050056 |
| | 6/6/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET CVR: THE INDEX SHOWS 10 MECHANICAL PLAN SHEETS |
| | (M-1- M-10), HOWEVER THERE ARE ONLY 6 PLAN SHEETS IN |
| | THE SETS (M-1- M-6). |
| | |
| | 2) PLEASE INDICATE HOW THE APARTMENTS ARE TO BE |
| | VENTILATED- NATURALLY IN ACCORDANCE WITH SECTION 402 |
| | FBC M, OR MECHANICALLY IN ACCORDANCE WITH SECTION 403 |
| | FBC M. THE CURRENT PLAN DOES NOT SHOW ANY OUTDOOR AIR |
| | BEING DUCTED INTO THE AIR HANDLERS SO THE ASSUMPTION IS |
| | NATURAL VENTILATION WILL BE THE MEANS. PLEASE CONFIRM |
| | AND PROVIDE CALCULATIONS IN COMPLIANCE WITH SECTION |
| | 402.2 FOR NATURAL, OR TABLE 403.3.1 FOR MECHANICAL. |
| | |
| | 3) THE ENERGYGAUGE COMPLIANCE SUBMITTAL NEEDS TO BE |
| | UPDATED TO THE SIXTH EDITION (2017) EDITION. PLEASE |
| | NOTE THAT THE REVISED SUBMITTAL MUST PROVIDE COMPLIANCE |
| | DATA FOR THE 2-TON AND 2.5 TON SYSTEMS WHICH IS MISSING |
| | FROM THE CURRENT SUBMITTAL. |
| | |
| | 4) SHEETS M-1, M-2, & M-3: THE AC CLOSET DOORS ON ALL |
| | FLOORS SHALL EITHER BE NON-COMBUSTIBLE OR SHALL HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50- SEE SECTION |
| | C403.2.9.2 FBC EC AND SECTION 602.2.1 FBC M. |
| | |
| | 5) M-1, M-2, M-3: THE TRANSFER DUCTS FROM THE BEDROOMS |
| | ARE UNDERSIZED BASED ON SECTION 601.6 (1) FBC M. THE |
| | CROSS-SECTIONAL AREA OF THE TRANSFER DUCTS SHALL BE |
| | 1-1/2 TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY |
| | DUCTS ENTERING THE ROOMS. |
| | |
| | 6) M-1, M-2, M-3: THE SIZES OF THE LINEAR DIFFUSERS AND |
| | GRILLS SHOWN ON THE PLAN APPEAR TO INCORRECT BECAUSE |
| | THE WIDTH MEASUREMENTS ARE SHOWN IN FEET INSTEAD OF |
| | INCHES. |
| | |
| | 7) M-1, M-2, M-3, M-4: THE TOILET EXHAUST SYSTEMS ARE |
| | CONFUSING BECAUSE THE FANS ARE LABELED TEF ON THE FLOOR |
| | PLANS, AND EF IN THE SCHEDULE. ARE THERE FANS IN THE |
| | BATHROOMS AND ON THE ROOFS? PLEASE CLARIFY. |
| | |
| | 8) M-6: PROVIDE TOILET EXHAUST RISER DRAWINGS SIMILAR |
| | TO THE DRYER EXHAUST RISER DETAIL. |
| | |
| | 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYERS |
| | PER SECTION 504.9 AND 913 FBC M, AND CORRECT THE PLANS |
| | TO SHOW COMPLIANCE WITH THE FOLLOWING REQUIREMENTS FOR |
| | COMMON DRYER EXHAUST SYSTEMS IN MULTISTORY STRUCTURES- |
| | SECTION 504.10: |
| | |
| | 1. THE SHAFT IN WHICH THE DUCT IS INSTALLED SHALL BE |
| | CONSTRUCTED AND FIRE-RESISTANCE RATED AS REQUIRED BY |
| | THE FLORIDA BUILDING CODE, BUILDING. |
| | 2. DAMPERS SHALL BE PROHIBITED IN THE EXHAUST DUCT. |
| | PENETRATIONS OF THE SHAFT AND DUCTWORK SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 607.5.5, EXCEPTION |
| | 2. |
| | 3 .RIGID METAL DUCTWORK SHALL BE INSTALLED WITHIN THE |
| | SHAFT TO CONVEY THE EXHAUST. THE DUCTWORK SHALL BE |
| | CONSTRUCTED OF SHEET STEEL HAVING A MINIMUM THICKNESS |
| | OF 0.0187 INCH (0.4712 MM) (NO. 26 GAGE) AND IN |
| | ACCORDANCE WITH SMACNA DUCT CONSTRUCTION STANDARDS. |
| | 4. THE DUCTWORK WITHIN THE SHAFT SHALL BE DESIGNED AND |
| | INSTALLED WITHOUT OFFSETS. |
| | 5. THE EXHAUST FAN MOTOR DESIGN SHALL BE IN ACCORDANCE |
| | WITH SECTION 503.2. |
| | 6. THE EXHAUST FAN MOTOR SHALL BE LOCATED OUTSIDE OF |
| | THE AIRSTREAM. |
| | 7. THE EXHAUST FAN SHALL RUN CONTINUOUSLY, AND SHALL BE |
| | CONNECTED TO A STANDBY POWER SOURCE. |
| | 8 .EXHAUST FAN OPERATION SHALL BE MONITORED IN AN |
| | APPROVED LOCATION AND SHALL INITIATE AN AUDIBLE OR |
| | VISUAL SIGNAL WHEN THE FAN IS NOT IN OPERATION. |
| | 9. MAKEUP AIR SHALL BE PROVIDED FOR THE EXHAUST SYSTEM. |
| | 10 .A CLEANOUT OPENING SHALL BE LOCATED AT THE BASE OF |
| | THE SHAFT TO PROVIDE ACCESS TO THE DUCT TO ALLOW FOR |
| | CLEANING AND INSPECTION. THE FINISHED OPENING SHALL BE |
| | NOT LESS THAN 12 INCHES BY 12 INCHES (305 MM BY 305 |
| | MM). SCREENS SHALL NOT BE INSTALLED AT THE TERMINATION. |
| | 11. THE COMMON MULTISTORY DUCT SYSTEM SHALL SERVE ONLY |
| | CLOTHES DRYERS AND SHALL BE INDEPENDENT OF OTHER |
| | EXHAUST SYSTEMS. |
| | |
| | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOK |
| | TOPS, OVENS, AND KITCHEN EXHAUST HOODS PER SECTIONS |
| | 917.2, AND 505.1 FBC M. |
| | |
| | 11) M5, M6: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR |
| | INSTALLATION OF THE ROOFTOP CONDENSERS AND STANDS, AND |
| | SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE |
| | STANDS- SECTION 301.15 FBC M. |
| | |
| | 12) THE ROOF MOUNTING CERTIFICATION DETAILS, AND LETTER |
| | FROM INGERSOLL RAND THAT ARE COPIED AND PASTED ON M-6 |
| | ARE OUTDATED AND ARE CITING THE OUTDATED CODE. PLEASE |
| | PROVIDE AN UPDATED COPY THAT IS RELEVANT TO THE CURRENT |
| | INSTALLATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |