Plan Review Notes
Plan Review Notes For Permit 18050056
Permit Number 18050056
Review Stop M
Sequence Number 1
Notes
Date Text
2018-06-06 16:47:201ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18050056
 6/6/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET CVR: THE INDEX SHOWS 10 MECHANICAL PLAN SHEETS
 (M-1- M-10), HOWEVER THERE ARE ONLY 6 PLAN SHEETS IN
 THE SETS (M-1- M-6).
  
 2) PLEASE INDICATE HOW THE APARTMENTS ARE TO BE
 VENTILATED- NATURALLY IN ACCORDANCE WITH SECTION 402
 FBC M, OR MECHANICALLY IN ACCORDANCE WITH SECTION 403
 FBC M. THE CURRENT PLAN DOES NOT SHOW ANY OUTDOOR AIR
 BEING DUCTED INTO THE AIR HANDLERS SO THE ASSUMPTION IS
 NATURAL VENTILATION WILL BE THE MEANS. PLEASE CONFIRM
 AND PROVIDE CALCULATIONS IN COMPLIANCE WITH SECTION
 402.2 FOR NATURAL, OR TABLE 403.3.1 FOR MECHANICAL.
  
 3) THE ENERGYGAUGE COMPLIANCE SUBMITTAL NEEDS TO BE
 UPDATED TO THE SIXTH EDITION (2017) EDITION. PLEASE
 NOTE THAT THE REVISED SUBMITTAL MUST PROVIDE COMPLIANCE
 DATA FOR THE 2-TON AND 2.5 TON SYSTEMS WHICH IS MISSING
 FROM THE CURRENT SUBMITTAL.
  
 4) SHEETS M-1, M-2, & M-3: THE AC CLOSET DOORS ON ALL
 FLOORS SHALL EITHER BE NON-COMBUSTIBLE OR SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50- SEE SECTION
 C403.2.9.2 FBC EC AND SECTION 602.2.1 FBC M.
  
 5) M-1, M-2, M-3: THE TRANSFER DUCTS FROM THE BEDROOMS
 ARE UNDERSIZED BASED ON SECTION 601.6 (1) FBC M. THE
 CROSS-SECTIONAL AREA OF THE TRANSFER DUCTS SHALL BE
 1-1/2 TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY
 DUCTS ENTERING THE ROOMS.
  
 6) M-1, M-2, M-3: THE SIZES OF THE LINEAR DIFFUSERS AND
 GRILLS SHOWN ON THE PLAN APPEAR TO INCORRECT BECAUSE
 THE WIDTH MEASUREMENTS ARE SHOWN IN FEET INSTEAD OF
 INCHES.
  
 7) M-1, M-2, M-3, M-4: THE TOILET EXHAUST SYSTEMS ARE
 CONFUSING BECAUSE THE FANS ARE LABELED TEF ON THE FLOOR
 PLANS, AND EF IN THE SCHEDULE. ARE THERE FANS IN THE
 BATHROOMS AND ON THE ROOFS? PLEASE CLARIFY.
  
 8) M-6: PROVIDE TOILET EXHAUST RISER DRAWINGS SIMILAR
 TO THE DRYER EXHAUST RISER DETAIL.
  
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYERS
 PER SECTION 504.9 AND 913 FBC M, AND CORRECT THE PLANS
 TO SHOW COMPLIANCE WITH THE FOLLOWING REQUIREMENTS FOR
 COMMON DRYER EXHAUST SYSTEMS IN MULTISTORY STRUCTURES-
 SECTION 504.10:
  
 1. THE SHAFT IN WHICH THE DUCT IS INSTALLED SHALL BE
 CONSTRUCTED AND FIRE-RESISTANCE RATED AS REQUIRED BY
 THE FLORIDA BUILDING CODE, BUILDING.
 2. DAMPERS SHALL BE PROHIBITED IN THE EXHAUST DUCT.
 PENETRATIONS OF THE SHAFT AND DUCTWORK SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 607.5.5, EXCEPTION
 2.
 3 .RIGID METAL DUCTWORK SHALL BE INSTALLED WITHIN THE
 SHAFT TO CONVEY THE EXHAUST. THE DUCTWORK SHALL BE
 CONSTRUCTED OF SHEET STEEL HAVING A MINIMUM THICKNESS
 OF 0.0187 INCH (0.4712 MM) (NO. 26 GAGE) AND IN
 ACCORDANCE WITH SMACNA DUCT CONSTRUCTION STANDARDS.
 4. THE DUCTWORK WITHIN THE SHAFT SHALL BE DESIGNED AND
 INSTALLED WITHOUT OFFSETS.
 5. THE EXHAUST FAN MOTOR DESIGN SHALL BE IN ACCORDANCE
 WITH SECTION 503.2.
 6. THE EXHAUST FAN MOTOR SHALL BE LOCATED OUTSIDE OF
 THE AIRSTREAM.
 7. THE EXHAUST FAN SHALL RUN CONTINUOUSLY, AND SHALL BE
 CONNECTED TO A STANDBY POWER SOURCE.
 8 .EXHAUST FAN OPERATION SHALL BE MONITORED IN AN
 APPROVED LOCATION AND SHALL INITIATE AN AUDIBLE OR
 VISUAL SIGNAL WHEN THE FAN IS NOT IN OPERATION.
 9. MAKEUP AIR SHALL BE PROVIDED FOR THE EXHAUST SYSTEM.
 10 .A CLEANOUT OPENING SHALL BE LOCATED AT THE BASE OF
 THE SHAFT TO PROVIDE ACCESS TO THE DUCT TO ALLOW FOR
 CLEANING AND INSPECTION. THE FINISHED OPENING SHALL BE
 NOT LESS THAN 12 INCHES BY 12 INCHES (305 MM BY 305
 MM). SCREENS SHALL NOT BE INSTALLED AT THE TERMINATION.
 11. THE COMMON MULTISTORY DUCT SYSTEM SHALL SERVE ONLY
 CLOTHES DRYERS AND SHALL BE INDEPENDENT OF OTHER
 EXHAUST SYSTEMS.
  
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOK
 TOPS, OVENS, AND KITCHEN EXHAUST HOODS PER SECTIONS
 917.2, AND 505.1 FBC M.
  
 11) M5, M6: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE ROOFTOP CONDENSERS AND STANDS, AND
 SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE
 STANDS- SECTION 301.15 FBC M.
  
 12) THE ROOF MOUNTING CERTIFICATION DETAILS, AND LETTER
 FROM INGERSOLL RAND THAT ARE COPIED AND PASTED ON M-6
 ARE OUTDATED AND ARE CITING THE OUTDATED CODE. PLEASE
 PROVIDE AN UPDATED COPY THAT IS RELEVANT TO THE CURRENT
 INSTALLATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719