| Date |
Text |
| 2018-05-07 17:02:04 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET CVR - THERE IS NOT INDICATION OF COMPLIANCE |
| | WITH ANY FIRE CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2013 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2013 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2013 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2013 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. |
| | |
| | PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN |
| | APPLICABLE REVISION NOTE. |
| | |
| | |
| | |
| | 2) THERE IS NO SHEET INDICATING THE LIFE SAFETY PLAN. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND |
| | SPECIFICATIONS TO ENSURE COMPLIANCE WITH APPLICABLE |
| | CODES AND |
| | STANDARDS. |
| | |
| | |
| | PLEASE PROVIDE A CCOMPLETE LIFE SAFETY PLAN THAT |
| | ILLUSTRATE OCCUPANT LOADS, TRAVEL DISTANCES, COMMON |
| | PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, |
| | EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE |
| | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES |
| | AND EQUIPMENT. |
| | |
| | |
| | |
| | |
| | 3) THERE IS NO INFORMATION REGARDING THE ELEVATORS. |
| | |
| | 30.5.3 ELEVATORS, ESCALATORS, AND CONVEYORS. ELEVATORS, |
| | ESCALATORS, AND CONVEYORS SHALL COMPLY WITH THE |
| | PROVISIONS OF |
| | SECTION 9.4. |
| | |
| | 9.4.2.3 ELEVATORS IN ACCORDANCE WITH ASME A17.7/CSA |
| | B44.7, |
| | PERFORMANCE-BASED SAFETY CODE FOR ELEVATORS AND |
| | ESCALATORS, |
| | SHALL BE DEEMED TO COMPLY WITH ASME A17.1/CSA B44, |
| | SAFETY |
| | CODE FOR ELEVATORS AND ESCALATORS, OR ASME A17.3, |
| | SAFETY CODE |
| | FOR EXISTING ELEVATORS AND ESCALATORS. |
| | |
| | 9.4.3 FIRE FIGHTERS? EMERGENCY OPERATIONS. |
| | 9.4.3.1 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE |
| | FIGHTERS? |
| | EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA |
| | B44, |
| | SAFETY CODE FOR ELEVATORS AND ESCALATORS. |
| | |
| | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN |
| | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL |
| | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET |
| | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER |
| | ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN |
| | AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE |
| | IN THE HORIZONTAL POSITION. |
| | |
| | |
| | |
| | |
| | 4) THERE IS NO INDICATION OF ELEVATORS BEING EQUIPPED |
| | WITH A REGION 7 KEYWAY. |
| | |
| | CHAPTER 399 FLORIDA STATUTES. SECTION 399.15, SECTION |
| | 17: |
| | REGIONAL EMERGENCY ELEVATOR ACCESS ? |
| | (1) IN ORDER TO PROVIDE EMERGENCY ACCESS TO ELEVATORS: |
| | (A) FOR EACH BUILDING IN THIS STATE WHICH IS SIX OR |
| | MORE STORIES IN HEIGHT, INCLUDING, BUT NOT LIMITED TO, |
| | HOTELS AND CONDOMINIUMS, ON WHICH A BUILDING PERMIT IS |
| | ISSUED AFTER SEPTEMBER 30, 2006, ALL OF THE KEYS FOR |
| | ELEVATORS THAT ALLOW PUBLIC ACCESS, INCLUDING, BUT NOT |
| | LIMITED TO, SERVICE AND FREIGHT ELEVATORS, MUST BE |
| | KEYED SO AS TO ALLOW ALL ELEVATORS WITHIN EACH OF THE |
| | SEVEN STATE EMERGENCY RESPONSE REGIONS TO OPERATE IN |
| | FIRE EMERGENCY SITUATIONS WITH ONE MASTER ELEVATOR KEY. |
| | |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT |
| | AND COMPLIANCE. |
| | |
| | |
| | |
| | 5) THERE IS NO INDICATION OF THE TRAVEL DISTANCE FROM |
| | THE ROOF TOP OBSERVATION DECK TO THE NEAREST EXIT. |
| | |
| | PER NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS |
| | |
| | 30.2.4 NUMBER OF MEANS OF EGRESS. |
| | 30.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL COMPLY |
| | WITH 7.4. |
| | |
| | |
| | 7.4* NUMBER OF MEANS OF EGRESS. |
| | 7.4.1 GENERAL. |
| | 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY, |
| | MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS |
| | THAN TWO, |
| | EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS: |
| | (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE |
| | PERMITTED |
| | IN CHAPTERS 11 THROUGH 43. |
| | (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A |
| | MEZZANINE |
| | OR BALCONY WHERE THE COMMON PATH OF TRAVEL LIMITATIONS |
| | OF |
| | CHAPTERS 11 THROUGH 43 ARE MET. |
| | |
| | 30.2.6.3.1 THE TRAVEL DISTANCE FROM A DWELLING UNIT |
| | (APARTMENT) |
| | ENTRANCE DOOR TO THE NEAREST EXIT SHALL NOT EXCEED 100 |
| | FT (30 M). |
| | |
| | PLEASE PROVIDE THE ACTUAL DIMENSION OF THE TRAVEL |
| | DISTANCE FROM THE REMOTE CORNER OF THE OBSERVATION DECK |
| | TO THE NEAREST EXIT INDICATING COMPLIANCE WITH THE |
| | ABOVE CODE. |
| | |
| | |
| | |
| | |
| | 6) SHEET 602, 603, 701 - THERE IS AN INDICATION OF A |
| | SPIRAL STAIR LEADING DOWN FROM THE OBSERVATION DECK. |
| | THIS APPEARS TO BE THE ONLY EXIT FROM THIS OCCUPIABLE |
| | FLOOR. |
| | |
| | SHOULD THE TRAVEL DISTANCE MEET THE REQUIRMENT ABOVE, |
| | THERE IS NO INDICATION THAT THE SPIRAL STAIRS MEET THE |
| | CODE. |
| | |
| | 30.2.2.3 STAIRS. |
| | 30.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE |
| | PERMITTED. |
| | 30.2.2.3.2 RESERVED. |
| | 30.2.2.3.3 SPIRAL STAIRS COMPLYING WITH 7.2.2.2.3 SHALL |
| | BE |
| | PERMITTED WITHIN EACH DWELLING UNIT. |
| | 30.2.2.3.4 WINDERS COMPLYING WITH 7.2.2.2.4 SHALL BE |
| | PERMITTED |
| | WITHIN EACH DWELLING UNIT. |
| | |
| | 7.2.2.2.3 SPIRAL STAIRS. |
| | 7.2.2.2.3.1 WHERE SPECIFICALLY PERMITTED FOR INDIVIDUAL |
| | OCCUPANCIES BY |
| | CHAPTERS 11 THROUGH 43, SPIRAL STAIRS SHALL BE |
| | PERMITTED AS A COMPONENT |
| | IN A MEANS OF EGRESS IN ACCORDANCE WITH 7.2.2.2.3.2 |
| | THROUGH 7.2.2.2.3.4. |
| | 7.2.2.2.3.2 SPIRAL STAIRS SHALL BE PERMITTED, PROVIDED |
| | THAT ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) RISER HEIGHTS SHALL NOT EXCEED 7 IN. (180 MM). |
| | (2) THE STAIRWAY SHALL HAVE A TREAD DEPTH OF NOT LESS |
| | THAN 11 IN. (280 |
| | MM) FOR A PORTION OF THE STAIRWAY WIDTH SUFFICIENT TO |
| | PROVIDE |
| | EGRESS CAPACITY FOR THE OCCUPANT LOAD SERVED IN |
| | ACCORDANCE WITH |
| | 7.3.3.1. |
| | (3) AT THE OUTER SIDE OF THE STAIRWAY, AN ADDITIONAL |
| | 10? IN. (265 MM) |
| | OF WIDTH SHALL BE PROVIDED CLEAR TO THE OTHER HANDRAIL, |
| | AND THIS |
| | WIDTH SHALL NOT BE INCLUDED AS PART OF THE REQUIRED |
| | EGRESS CAPACITY. |
| | (4) HANDRAILS COMPLYING WITH 7.2.2.4 SHALL BE PROVIDED |
| | ON BOTH SIDES |
| | OF THE SPIRAL STAIRWAY. |
| | (5) THE INNER HANDRAIL SHALL BE LOCATED WITHIN 24 IN. |
| | (610 MM), |
| | MEASURED HORIZONTALLY, OF THE POINT WHERE A TREAD DEPTH |
| | OF NOT LESS |
| | THAN 11 IN. (280 MM) IS PROVIDED. |
| | (6) THE TURN OF THE STAIRWAY SHALL BE SUCH THAT THE |
| | OUTER HANDRAIL IS AT |
| | THE RIGHT SIDE OF DESCENDING USERS. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 7) A SHEETS - THERE IS NO INDICATION OF THE EXIT |
| | STAIRWELLS BEING 1 HOUR FIRE RATED. |
| | |
| | PER NFPA 101, CHAPTER 30 |
| | |
| | 30.2.2 MEANS OF EGRESS COMPONENTS. |
| | 30.2.2.1 GENERAL. |
| | 30.2.2.1.1 COMPONENTS OF MEANS OF EGRESS SHALL BE |
| | LIMITED TO THE |
| | TYPES DESCRIBED IN 30.2.2.2 THROUGH 30.2.2.12. |
| | 30.2.2.1.2 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH 30.3.5, |
| | EXIT ENCLOSURES SHALL HAVE A MINIMUM 1-HOUR FIRE |
| | RESISTANCE RATING, |
| | AND DOORS SHALL HAVE A MINIMUM 1-HOUR FIRE PROTECTION |
| | RATING. |
| | |
| | PLEASE PROVIDE DETAILS AND INDICATIONS |
| | |
| | |
| | |
| | 8) SHEET A 601 - THERE ARE NO INDICATIONS THAT THE DOOS |
| | OF THE STAIRWELLS ARE 1 HOUR FIRE RATED IN THE DOOR |
| | SCHEDULE. |
| | |
| | 30.2.2 MEANS OF EGRESS COMPONENTS. |
| | 30.2.2.1 GENERAL. |
| | 30.2.2.1.1 COMPONENTS OF MEANS OF EGRESS SHALL BE |
| | LIMITED TO THE |
| | TYPES DESCRIBED IN 30.2.2.2 THROUGH 30.2.2.12. |
| | 30.2.2.1.2 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH 30.3.5, |
| | EXIT ENCLOSURES SHALL HAVE A MINIMUM 1-HOUR FIRE |
| | RESISTANCE RATING, |
| | AND DOORS SHALL HAVE A MINIMUM 1-HOUR FIRE PROTECTION |
| | RATING. |
| | |
| | PLEASE PROVIDE DETAILS |
| | |
| | |
| | |
| | 9) SHEET A 601 - THERE ARE NO INDICATION OF ANY DOOR |
| | HARDWARE IN THE DOOR SCHEDULE. |
| | |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | |
| | 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE. |
| | 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE |
| | EQUIPPED WITH |
| | PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL MEET |
| | ALL OF THE |
| | FOLLOWING CRITERIA: |
| | (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE |
| | ACTUATING |
| | PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF |
| | OF THE |
| | WIDTH OF THE DOOR LEAF. |
| | (2) IT SHALL BE MOUNTED AS FOLLOWS: |
| | (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN. |
| | (865 MM), |
| | AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. |
| | (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30 |
| | IN. (760 MM), |
| | AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. |
| | (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE |
| | NOT TO EXCEED |
| | 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND |
| | LATCHES. |
| | 7.2.1.7.2* ONLY APPROVED FIRE EXIT HARDWARE SHALL BE |
| | USED ON FIRE |
| | PROTECTION-RATED DOOR ASSEMBLIES. NEW PANIC HARDWARE |
| | AND NEW |
| | FIRE EXIT HARDWARE SHALL COMPLY WITH ANSI/UL 305, |
| | STANDARD FOR |
| | SAFETY PANIC HARDWARE, AND ANSI/BHMA A156.3, EXIT |
| | DEVICES. |
| | |
| | 7.2.1.8 SELF-CLOSING DEVICES. |
| | 7.2.1.8.1* A DOOR LEAF NORMALLY REQUIRED TO BE KEPT |
| | CLOSED SHALL |
| | NOT BE SECURED IN THE OPEN POSITION AT ANY TIME AND |
| | SHALL BE SELFCLOSING |
| | OR AUTOMATIC-CLOSING IN ACCORDANCE WITH 7.2.1.8.2, |
| | UNLESS |
| | OTHERWISE PERMITTED BY 7.2.1.8.3. |
| | |
| | PLEASE PROVIDE FOR THE APPLICABLE HARDWARE OF EACH TYPE |
| | OF DOOR. |
| | |
| | |
| | |
| | |
| | 10) THERE ARE NO INDICATION OF ANY 61G DOCUMENTS FOR |
| | FIRE SPRINKLERS. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION |
| | ENGINEERING |
| | DOCUMENTS. |
| | (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED |
| | IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE |
| | WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND |
| | DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S), |
| | MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND |
| | UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE |
| | SAFEGUARDING OF LIFE, HEALTH OR PROPERTY. |
| | (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE |
| | ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND |
| | COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES |
| | AND STANDARDS, WHERE AVAILABLE. |
| | (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A |
| | SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION |
| | SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE |
| | PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT |
| | AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE |
| | TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND |
| | ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT |
| | SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED |
| | BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE |
| | FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL |
| | BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS. |
| | (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION |
| | FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT |
| | COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED |
| | ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER |
| | OF RECORD FOR THE FIRE PROTECTION SYSTEM. |
| | (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS, |
| | SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY |
| | RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN |
| | ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS, |
| | UNLESS SHOWN ON OTHER RELATED DOCUMENTS. |
| | (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER |
| | OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION |
| | IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED |
| | PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE |
| | SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR |
| | OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE |
| | SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED |
| | 4-2-2000, 6-26-01 |
| | |
| | 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION |
| | SYSTEMS. |
| | (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT |
| | ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, |
| | DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE |
| | CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE |
| | WATER MAINS AND DEDICATED FIRE PROTECTION WATER |
| | SOURCES. |
| | (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL |
| | INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN |
| | APPLICABLE: |
| | (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER |
| | SUPPLY AS DEFINED BY 633.021(18) F.S. |
| | (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE |
| | CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING |
| | STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND |
| | CONCLUSIONS. |
| | (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA. |
| | (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, |
| | DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR |
| | EACH SEPARATE 42 HAZARD OCCUPANCY. |
| | (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS |
| | MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR |
| | CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE |
| | NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM |
| | DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY |
| | DEMANDING DESIGN AREA. |
| | (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE |
| | FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO |
| | CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, |
| | STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH |
| | RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND |
| | LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF |
| | SERVICE. |
| | (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE |
| | POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF |
| | WATER. |
| | (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF |
| | RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER |
| | SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION |
| | (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE |
| | LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY |
| | WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY |
| | TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND |
| | THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE |
| | PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE |
| | MEASURES. |
| | (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND |
| | DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS |
| | INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. |
| | (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD |
| | AND INTERIOR FIRE PROTECTION COMPONENTS. |
| | (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE |
| | MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL |
| | DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING |
| | APPROVAL AND DOCUMENTATION. |
| | (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE |
| | INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE |
| | OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL |
| | ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE |
| | CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED |
| | 4-2-2000, 6-26-01, 7-12-05 |
| | |
| | THESE DOCUMENTS, IN NARRATIVE OR DRAWINGS WITH THE |
| | ABOVE REQUIRED INFORMATION SHALL BE SUBMITTED WITH THIS |
| | MASTER PERMIT, SHOP DRAWINGS CAN THEN BE DEVELOPED AND |
| | SUBMITTED UNDER SEPARATE PERMITS. |
| | |
| | |
| | |
| | |
| | 11 ) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 12) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | 30.2.2.2.4 APARTMENT OCCUPANCIES SHALL BE EXEMPT FROM |
| | THE REENTRY |
| | PROVISIONS OF 7.2.1.5.8 WHERE THE EXIT ENCLOSURE SERVES |
| | DIRECTLY ONLY ONE DWELLING UNIT PER FLOOR, AND SUCH |
| | EXIT IS A |
| | SMOKEPROOF ENCLOSURE IN ACCORDANCE WITH 7.2.3. |
| | |
| | |