| Plan Review Notes For Permit 18050054 |
| Permit Number |
18050054 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-03 13:04:22 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | AIC RATING FOR THE SERVICE. | | | PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT | | | AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC | | | 110.10 | | | | | | PLEASE SHOW LOCATION OF ANY OTHER SERVICES ON THE | | | BUILDING. 230.72 FOR GROUPING OF MAINS. | | | | | | PLEASE SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE | | | PANEL IN THE BUILDING. | | | | | | | | | |
|