2018-05-01 18:23:03PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY WHICH FASTENING OPTION WILL BE USED FOR THE
 E(9) SYSTEM TYPE FROM PAGE 66 OF THE PRODUCT APPROVAL.
 FBC 107.2.1 & FBC 1609.1
  
 2) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE. FBC
 107.2.1 & FBC 1609.1
  
 3) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING OF THE BASE SHEET AS REQUIRED BY
 GENERAL LIMITATION NUMBER 7 ON PAGE 67 OF NOA NO.
 15-1020.01. FBC 107.2.1.2 & FBC 1609.1