| Plan Review Notes For Permit 18050052 |
| Permit Number |
18050052 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-01 18:23:03 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY WHICH FASTENING OPTION WILL BE USED FOR THE | | | E(9) SYSTEM TYPE FROM PAGE 66 OF THE PRODUCT APPROVAL. | | | FBC 107.2.1 & FBC 1609.1 | | | | | | 2) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE. FBC | | | 107.2.1 & FBC 1609.1 | | | | | | 3) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | ENHANCED FASTENING OF THE BASE SHEET AS REQUIRED BY | | | GENERAL LIMITATION NUMBER 7 ON PAGE 67 OF NOA NO. | | | 15-1020.01. FBC 107.2.1.2 & FBC 1609.1 |
|