| 2018-08-06 06:33:36 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 4X THE PLAN REVIEW FEE HAS BEEN ADDED TO THIS FOR THE |
| | SAME DEFECIENCIES ON PLAN REVIEW DOCUMENTS FOR 6 |
| | REVIEWS AS PER F.S. 553.802B |
| | |
| | 1. 6TH PLAN REVIEW WITH SAME DEFICIENCIES. |
| | |
| | 2. HIGH VOLTAGE AND LOW VOLTAGE TOGETHER IN J-BOX. |
| | 725.136B NEC |
| | |
| | 3. DISCONNECT REQUIRED WITHIN SIGHT OF SIGN THAT |
| | DISCONNECTS THE BRANCH CIRCUIT/FEEDER CONDUCTORS BEFORE |
| | IT ENTERS THE SIGN. NEC 600.6A1 |
| | |
| | 4. DUE TO THE DISCONNECT REQUIREMENTS OF 600.6A(1) NEC |
| | AN ELEC SUB-PERMIT CAN'T BE ISSUED TO AN ES LICENSE |
| | HOLDER BECAUSE IT IS OUT OF THE SCOPE OF WORK FOR THEIR |
| | LICENSE. PLEASE HAVE LICENSED ELECTRICIAN PULL |
| | SUB-ELECTRICAL PERMIT. |
| | |
| | SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C. |
| | 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN |
| | SPECIALTY CONTRACTOR) |
| | |
| | THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL |
| | FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION, |
| | INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF |
| | ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF |
| | CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR |
| | ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR |
| | TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER |
| | THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE |
| | REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE |
| | BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY |
| | STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN |
| | TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250) |
| | VOLTS MAXIMUM. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |
| | [email protected] |
| | CELL: 561-657-1653 |