| 2018-07-25 06:24:37 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. 5TH PLAN REVIEW WITH SAME DEFICIENCIES. THERE WILL |
| | BE NO FURTHER PLAN REVIEWS OF THIS PERMIT (FOR |
| | ELECTRICAL) UNTIL I HAVE SPOKEN TO EITHER THE QUALIFIER |
| | FOR FERRIGN SIGNS OR THE ENGINEER OF RECORD FOR THIS |
| | PROJECT. PLEASE CONTACT ME DIRECTLY ON MY CELL PHONE |
| | 561-657-1653 |
| | |
| | 2. HIGH VOLTAGE AND LOW VOLTAGE TOGETHER IN J-BOX. |
| | 725.136B NEC |
| | |
| | 3. DISCONNECT REQUIRED AS PER NEC 600.6A1 |
| | |
| | 4. DUE TO THE DISCONNECT REQUIREMENTS OF 600.6A(1) NEC |
| | AN ELEC SUB-PERMIT CAN'T BE ISSUED TO AN ES LICENSE |
| | HOLDER BECAUSE IT IS OUT OF THE SCOPE OF WORK FOR THEIR |
| | LICENSE. |
| | |
| | SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C. |
| | 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN |
| | SPECIALTY CONTRACTOR) |
| | |
| | THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL |
| | FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION, |
| | INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF |
| | ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF |
| | CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR |
| | ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR |
| | TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER |
| | THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE |
| | REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE |
| | BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY |
| | STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN |
| | TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250) |
| | VOLTS MAXIMUM. |
| | |
| | 5. THERE IS A NOTE ON THE PLAN THAT STATES "TIME CLOCK |
| | IS EXISTING" TIME CLOCK MUST STILL CONFORM TO FBC CE |
| | 405.2.4 (ASTRONOMICAL TIME CLOCK NEEDED) |
| | |
| | 6. SIGNATURE AND SEAL ON PLAN IS PHOTO COPIED. NOT |
| | CONSIDERED TO BE SIGNED AND SEALED. |
| | |
| | PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE |
| | LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S |
| | SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| | COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED |
| | ON PHYSICALLY TRANSMITTED DOCUMENTS. |
| | CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL |
| | SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON |
| | EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE, |
| | DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S |
| | SIGNATURE SHALL NOT BE USED. |
| | |
| | AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED |
| | DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A |
| | WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART |
| | OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO |
| | PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT |
| | THE SIGNATURE IS NOT MADE ILLEGIBLE. |
| | CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN |
| | USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN |
| | EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE |
| | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| | SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE |
| | SIGNATURE ILLEGIBLE. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |