| 2018-06-03 09:41:40 | 1) THE SUBMITTED GAS PLAN SHOWS AN EXISTING 3/4 INCH |
| | GAS LINE FROM THE METER SUPPLYING AN 1 1/4 INCH |
| | GALVANIZED. PROVIDE ADDITIONAL DETAILS AS TO HOW THIS |
| | FEAT WILL BE ACCOMPLISHED.THE EXISTING PLANS ON FILE |
| | SHOW AN 1 1/2 INCH GALVANIZED PIPE AT THE METER. |
| | 2) THE SUBMITTED GAS PLAN SHOWS A 12 INCH WATER COLUMN |
| | NATURAL GAS METER BUT THERE IS ALSO A NOTE STATING IT |
| | IS A 2 PSI SYSTEM. WHICH IS IT? CLARIFY. |
| | 3) SHOW THE DISTANCE FROM THE OUTLET OF THE GAS METER |
| | TO THE MOST REMOTE GAS OUTLET INTO THE STRUCTURE AND |
| | THE LOAD ON THAT SECTION.2017 FBCR SEC. G2413.4.1. THE |
| | EXISTING PLANS ON FILE WITH THE CITY SHOW A DISTANCE OF |
| | 200 FEET FROM THE METER TO THE FURTHEST OUTLET ON THE |
| | SYSTEM WHICH IS THE POOL HEATER. THIS DISTANCE SHALL BE |
| | USED FOR THE SIZING OF THIS SYSTEM. |
| | 4) THE MINIMUM SIZE SCH. 40 METALLIC PIPE AT THE METER |
| | SHALL BE 2 1/2 INCHES PER THE TOTAL BTU LOAD AND THE |
| | DISTANCE FROM THE METER TO THE MOST REMOTE OUTLET.2017 |
| | FBCR SEC. G2413.4.1, TABLE G2413.4 (1). |
| | 5) IF THIS IS A LOW PRESSURE SYSTEM, WHY ARE YOU |
| | SUBMITTING SPECS FOR REGULATORS? CLARIFY. |
| | 6) IF THIS IS GOING TO BE A 2 PSI SYSTEM SUBMIT THE |
| | APPLICABLE SIZING TABLE FOR THE SYSTEM AND SHOW THE |
| | DISTANCE FROM EACH MP REGULATOR TO THE FURTHEST OUTLET |
| | AND BTU LOAD ON THAT SECTION. 2017 FBCR SEC. G2413.4.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | |