| Plan Review Notes For Permit 18050021 |
| Permit Number |
18050021 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-06-03 07:52:56 | 1) SHOW THE DISTANCE OF THE EXISTING GAS LINE FROM THE | | | GAS METER TO THE FURTHEST GAS OUTLET ON THE SYSTEM.THE | | | EXISTING PLAN ON FILE IN CITY RECORDS SHOWS 88 FEET TO | | | THE FURTHEST OUTLET. THIS DISTANCE SHALL BE USED FOR | | | SIZING THE PIPING FOR THE GENERATOR AND FOR THE CHEKING | | | THE EXISTING SYSTEM.IF UNDERSIZED, THE EXISTING SYSTEM | | | MUST BE REDONE TO ENSURE A SAFE OPERATING SYSTEM WPB | | | AMEND. TO FBC SEC. 107.2.1, | | | 2) HOW DO YOU PLAN ON SUPPLYING AN 1 1/4 INCH LINE WITH | | | A 3/4 INCH LINE AT THE OUTLET OF THE GAS METER? THE | | | LINE AT THE OUTLET OF THE METER SHALL BE A MINIMUM OF 1 | | | 1/2 INCHES AS SHOWN ON THE EXISTING PLAN ON FILE WITH | | | THE CITY. | | | 3) THE EXISTING PLAN ON FILE WITH THE CITY ALSO SHOWS A | | | FUTURE BBQ THAT NEEDS TO BE LISTED AND ADDED ON THE BTU | | | LOAD OF THE SUBMITTED GAS PLAN.2017 FBCR SEC. G2412.3, | | | G2412.4. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | |
|