| Plan Review Notes For Permit 18050016 |
| Permit Number |
18050016 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-06-03 08:46:16 | 1) THE EXISTING PLANS ON FILE WITH THE CITY SHOW A BBQ | | | GRILL AND ALSO A POOL HEATER. THE BTU LOADS OF THESE | | | APPLIANCES MUST BE ADDED INTO THE TOTAL BTU LOAD FOR | | | THIS SYSTEM. 2017 FBCR SEC. G2412.3, 2412.4 G2412.8. IF | | | UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO | | | ENSURE A SAFE OPERATING SYSTEM. | | | 2) THE SHUTOFF VALVE ON THE LINE TO THE INTERIOR OF THE | | | STRUCTURE SHALL BE LOCATED IMMEDIATELY AHEAD OF THE | | | REGULATOR, NOT AFTER THE REGULATOR. 2017 FBCR SEC. | | | G2420.4. | | | 3) SHOW THE DISTANCE FROM THE MP REGULATOR FOR THE | | | EXISTING LOAD INTO THE STRUCTURE TO THE FURTHEST OUTLET | | | ON THAT SECTION OF THE SYSTEM. COMPLY WITH 2017 FBCR | | | SEC. G2413.4.1. | | | 4) INDICATE ON THE PLANS WHICH GAS SIZING TABLE IS USED | | | FOR THE LOW PRESSURE SYSTEM. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | |
|