| Plan Review Notes For Permit 18050006 |
| Permit Number |
18050006 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-03 14:18:24 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | 240.87 ARC ENERGY REDUCTION | | | WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR | | | WHICH THE | | | ACTUAL OVERCURRENT DEVICE INSTALLED IN A CIRCUIT | | | BREAKER IS RATED | | | OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND | | | (B) SHALL | | | APPLY. | | | (A) DOCUMENTATION. DOCUMENTATION SHALL BE AVAILABLE TO | | | THOSE | | | AUTHORIZED TO DESIGN, INSTA LL, OPERATE, OR INSPECT THE | | | INSTALLATION | | | AS TO THE LOCATION OF THE CIRCUIT BREAKER(S). | | | (B) METHOD TO REDUCE CLEARING TIME. ONE OF THE | | | FOLLOWING | | | OR APPROVED EQUIVALENT MEANS SH ALL BE PROVIDED: | | | (1) ZONE-SELECTIVE INTERLOCKING | | | (2) DIFFERENTIAL RELAYING | | | (3) ENERGY-REDUCING MAINTENANCE SWITCHING WITH LOCAL | | | STATUS | | | INDICATOR | | | (4) ENERGY-REDUCING ACTIVE ARC FLASH MITIGATION SYSTEM | | | (5) AN APPROVED EQUIVALENT MEANS |
|