| 2018-05-19 08:59:33 | NONE OF THE COMMENTS BELOW HAVE BEEN ADDRESSED FROM THE |
| | FIRST REVIEW. COMPLY WITH ALL PREVIOUS COMMENTS. |
| | |
| | 1) THE COPIES OF THE GAS SIZING TABLES THAT HAVE BEEN |
| | SUBMITTED ARE FROM THE 2014 FBC-FUEL GAS. SUBMIT THE |
| | PROPER SIZING TABLES FROM THE 2017 FBC-FUEL GAS. THESE |
| | TABLES HAVE CHANGED IN THE 2017 FBC-FUEL GAS SO ENSURE |
| | YOU CHECK THAT THE TABLES YOU ARE SUBMITTING ARE |
| | CORRECT. TABLE 402.4 (6) FOR SCH. 40 METALLIC PIPE IN |
| | THE 2017 CODE HAS AN INLET PRESSURE OF 3 PSI WITH A |
| | PRESSURE DROP OF 2.0 PSI AND TABLE 402.4 (22) FOR PE |
| | PIPE IN THE 2017 FBC-FUEL GAS IS FOR AN INLET PRESSURE |
| | OF 2 PSI WITH A PRESSURE DROP OF 1.0 PSI. IT IS OBVIOUS |
| | YOU CANNOT USE THESE TABLES THAT YOU HAVE SUBMITTED. |
| | ***NOTE*** |
| | PLEASE DO NOT TRY TO ENLARGE THE GAS SIZING TABLES. THE |
| | PROCESS IS MAKING THE TABLES BLURRED AND VERY DIFFICULT |
| | TO READ. |
| | 2) THE GAS DRAWING APPEARS TO SHOW A SECOND STAGE |
| | REGULATOR JUST DOWNSTREAM OF THE GAS METER ON THE |
| | CONSUMER SIDE. WHY WOULD IT BE LOCATED AT THE OUTLET OF |
| | THE GAS METER? THAT WOULD MAKE THE PSI TO THE EXISTING |
| | POOL HEATER LESS THAN 2 PSI. CLARIFY. |
| | 3) THE GAS RISER IS SHOWING AN 1 1/4 INCH LINE AT 2 PSI |
| | TO THE EXISTING POOL HEATER WITH A 3/4 INCH SHUTOFF |
| | VALVE. CLARIFY. |
| | 4) IS THE EXISTING 1 1/4 INCH GALVANIZED LINE |
| | UNDERGROUND? I UNDERSTAND IT IS EXISTING BUT GALVANIZED |
| | PIPING IS NOT PERMITTED TO BE INSTALLED UNDERGROUND. |
| | ZINC COATINGS (GALVANIZING)SHALL NOT BE DEEMED ADEQUATE |
| | PROTECTION FOR GAS PIPING UNDERGROUND. 2017 FBC-FUEL |
| | GAS SEC.404.11. |
| | IN THE FUTURE, PLEASE ATTEMPT TO SUBMIT GAS DRAWINGS |
| | THAT ARE EXPANDED SO THAT ALL THE INFORMATION IS NOT |
| | CRAMMED TOGETHER . WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | NOTE: I SUGGEST THE A REPRESENTATIVE FROM DIG IT |
| | UNLIMITED CONTACT ME TO SET UP A MEETING TO GO OVER |
| | THESE COMMENTS BECAUSE THE COMMENT REGARDING THE SIZING |
| | TABLES IS APPEARING IN OTHER PLAN REVIEWS FOR DIG IT |
| | AND I WOULD LIKE TO GET THE ISSUE RESOLVED SO WE CAN |
| | TRY TO GET YOUR PERMITS ISSUED AND GET YOUR PROJECTS |
| | GOING. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | CITY OF WEST PALM BEACH |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |