Plan Review Notes
Plan Review Notes For Permit 18041372
Permit Number 18041372
Review Stop B
Sequence Number 1
Notes
Date Text
2018-05-14 15:40:12PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE A STEEL REINFORCING DETAIL FOR THE POOL
 STEPS. FBC 107.2.1
  
 2) THE POOL ALARMS ARE REQUIRED TO COMPLY WITH UL 2017,
 NOT UL 2107. PLEASE CORRECT THE NOTE ON SHEET 3 OF THE
 DRAWINGS. SEE FBC-R SECTION 4501.17.1.19.
  
 3) ON OCTOBER 5, 2017, THE CITY OF WEST PALM BEACH
 ADOPTED A (2) TWO FOOT FREEBOARD ABOVE THE BASE FLOOD
 ELEVATION. ALTHOUGH THIS PROPERTY IS NOT LOCATED IN A
 SPECIAL FLOOD HAZARD AREA, YOU SHOULD REVISE THE NOTE
 ON SHEET 3 OF THE DRAWINGS FOR FUTURE SUBMITTAL
 DOCUMENTS.