| 2018-06-08 12:21:44 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR WALL.THE |
| | REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM AND |
| | EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 |
| | INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE |
| | OTHER SIDE. |
| | |
| | 2. TOILET PAPER DISPENSERS OUTLET OF THE DISPENSER |
| | SHALL BE 15 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR . PER FBC ACC 604.7 |
| | |
| | 3.PLEASE LABEL DIMENSIONS ON THE CLEAR SPACE FOR THE |
| | TOILET LAVATORY AND WATER FOUNTAIN. PER FBC ACC 604.3.1 |
| | , 606.2 , 602.2 |
| | |
| | 4. SHT.LS-1 SHOWS A TABLE AND CHAIRS ENCROACHING INTO |
| | THE CLEAR FLOOR SPACE OF THE WATER FOUNTAIN PLEASE SHAW |
| | THE CLEAR FLOOR SPACE CLEAR OF ANY OBSTRUCTIONS. PER |
| | FBC ACC 606.2 |
| | |
| | 5. THE SINK IN THE BUSINESS LOUNGE SHALL COMPLY WITH |
| | FBC ACC 606.2, 606.3 |
| | |
| | 6. SHT. P0.1 THE DRINKING FOUNTAIN IS MISSING FROM THE |
| | WATER AND SANITARY ISOMETRIC PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.3.5.1.3 |
| | |
| | 7. ON THE SANITARY RISER THE DRINKING FOUNTAIN AND THE |
| | BREAK ROOM SINK SHALL CONNECT DOWN STREAM OF THE |
| | BATHROOM GROUPS WET VENTS. PER FBC ACC 912.1 |
| | |
| | 8. ONLY THE FIXTURES OF 2 BATHROOM GROUP CAN CONNECT TO |
| | A SINGLE WET VENT SYSTEM AS IT IS DRAIN NOW THERE IS 3 |
| | THE EXECUTIVE BATHROOM SHOULD BE VENT BY THE LAVATORY |
| | AND INCLUDE THE TOILET AND SHOWER CONNECTED TO THAT |
| | BRANCH. PER FBC PL 912.1, 912.2.1 |
| | |
| | 9. THE SHOWER SHALL COMPLY WITH FBC ACC 608 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |