| Date |
Text |
| 2018-05-29 15:20:53 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18041368 |
| | 5/29/18 |
| | |
| | CODES IN EFFECT: |
| | FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SECTION 301.15 FBC MC- WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. PLEASE PROVIDE DETAILS AND |
| | SUBMIT A FL, PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE |
| | ROOF STANDS- RULE 9N-3 FAC |
| | |
| | 2) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR |
| | HANDLERS- SECTION 307.2 FBC MC |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | |