| Plan Review Notes For Permit 18041364 |
| Permit Number |
18041364 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-07 07:57:00 | 05/07/2018 1ST GAS REVIEW**DENIED** | | | | | | 1) PLANS THAT BEAR THE TILTE BLOCK OF A LICENSE | | | ENGINEER REQUIRES PLANS TO BE SEALED AND SIGED PER FL | | | ADMIN CODE 61G15-23.001 | | | | | | 2) SUPPLY TANKLESS INSTALLATION MANUAL SHOW MIN | | | DISTANCE REQUIRED FROM A DOOR OR WINDOW THAT OPEN'S. | | | SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | | | | 3) SUPPLY WHAT APPROVING BODIES THE STOVE IS LISTED AND | | | LABEL UNDER. GAS APPLIANCES SHALL BE LISTED AND | | | LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | | | | 4) THE PLAN SHOW TANKLESS WATER HEATER IN 3 DIFFERENT | | | LOCATION'S FOR A TOTAL OF 4. YOUR PERMIT APPLICATION IS | | | FOR 2 HWH. PLEASE REVISE PLAN TO CLEARIFY. FBC 107.2.1 | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|