| Plan Review Notes For Permit 18041346 |
| Permit Number |
18041346 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-05-14 07:17:45 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. OK | | | | | | 2. COMMENT FROM FIRST REVIEW: FBC B 1609, PROVIDE | | | INFORMATION REGARING THE GLASS INSTALLATION - TYPE OF | | | GLASS, FASTENING, ETC. | | | | | | 2ND REVIEW, ILLEGIBLE SBCCI REPORT WAS PROVIDED; PLEASE | | | PROVIDE LEGIBLE REPORTS. ALSO HAVE ENGINEER OF RECORD | | | REVIEW THE PRODUCT APPROVALS PRIOR TO SUBMITTING. | | | | | | 3. COMMENT FROM PREVIOUS LIST, REVISE PLAN TO INCLUDE | | | WIND DESIGN CRITERIA FBC B 1603.1.4. | | | | | | 2ND REVIEW, INCLUDE WIND LOADS ON GLASS. | | | | | | | | | |
|