| 2018-06-06 13:11:36 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. RISER DIAGRAM SHOWS PANEL A, BUT THIS PANEL IS NOT |
| | SHOWN ON THE PLAN. THERE IS A PANEL B SHOWN ON PLAN AND |
| | THERE IS A PANEL SCHEDULE FOR PANEL B BUT IT IS NOT |
| | SHOWN ON THE RISER DIAGRAM. SHOW LOCATION OF ALL |
| | ELECTRICAL PANELS ON PLAN. ALSO, PROVIDE PANEL SCHEDULE |
| | FOR PANEL A WITH A LOAD CALCULATION. PROVIDE CORRECTION |
| | TO LOAD CALCULATION FOR PANEL B, ONE OF THE RTU'S IN |
| | NOT INCLUDED SO THE MATH IS WRONG. WPB FBC 107.2.1; NEC |
| | 215.5, 220, 408.4 |
| | 2. PROVIDE AIC RATING OF NEW PANEL. NEC 110.3, 110.9 |
| | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | |
| | NEW COMMENT: |
| | |
| | 4. PLEASE BE ADVISED THAT THIS COMMENT HAS NOT BEEN |
| | ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF |
| | IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD |
| | TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS |
| | REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO |
| | EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A |
| | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)? |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |