| 2018-05-09 17:31:26 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18041305 |
| | 5/9/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | SOME OF THE COMMENTS BELOW ALSO APPEAR ON PERMIT |
| | #18041229 BECAUSE THE PLANS ARE BOTH TITLED "VANILLA |
| | SHELL BUILDOUT", THE APPLICATIONS SHOW THE SAME WORK |
| | DESCRIPTION, AND BOTH PLANS SHOW THE SAME RTU |
| | INSTALLATIONS. |
| | |
| | 1) REPLACEMENT OF THE AC SYSTEMS ARE NOT EXACT SAME |
| | SIZE REPLACEMENTS SO COOLING AND HEATING CALCULATIONS |
| | ARE REQUIRED TO VERIFY ACCURATE SIZING- SECTION |
| | C403.2.1 FBC-14 ENERGY CONSERVATION. |
| | |
| | 2) SHEET C-1, NOTE 3 & SHEET 4.0M: SHOW THE LOCATIONS |
| | OF THE ROOFTOP HOODS AND PROVIDE CAPPING DETAILS. |
| | |
| | 3) 4.0M: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| | SUPPLY SYSTEMS OF THE NEW 5-TON RTU'S , UNLESS |
| | MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEMS |
| | CANNOT PRODUCE OVER 2000 CFMS OF SUPPLY AIR- SECTION |
| | 606.2.1. |
| | |
| | 4) 4.0M: THE CONDENSATE PIPING SHALL BE SUPPORTED AT |
| | MAXIMUM 4' INTERVALS- TABLE 305.4. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |