| 2018-05-21 09:49:23 | SHELL ONLY, BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- PROVIDE ALL THE WIND DESIGN DATA AS REQUIRED BY SEC. |
| | 1603.1.4 FBC. |
| | |
| | SEC. 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | 1.ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | 2.RISK CATEGORY. |
| | 3.WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE THAN |
| | ONE WIND EXPOSURE IS UTILIZED. |
| | 4.APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | 5.DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF |
| | (KN/M2). |
| | |
| | 2- A) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED |
| | BY FAC 61G20-3.001 FOR THE NEW EXTERIOR DOOR #1. |
| | |
| | B) DOOR #2 SHOWN ON FLOOR PLAN DOESN'T MATCH DOOR SHOWN |
| | ON THE DOOR SCHEDULE ON SHEET 1.0A. REVISE AS REQUIRED |
| | TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| | |
| | 4- REVISE OCCUPANT LOAD NUMBER. NUMBER OF PEOPLE IS |
| | ROUNDED UP NOT ROUNDED DOWN. 3475 SF DIVIDED BY 100 |
| | EQUALS 34.75. THEREFORE NUMBER OF PEOPLE IS 35. REVISE |
| | AS REQUIRED. TABLE 1004.1.2 FBC. |
| | |
| | 5- SHEET 1.0A: |
| | A) DOOR FOR ACCESSIBLE RESTROOM LOCATED IN THE CENTER |
| | OF THE TENANT SPACE SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE OF THE LAVATORY. REVISE AS REQUIRED. SEC. |
| | 603.2.3 FBC-ACCESSIBILITY. |
| | |
| | B) PROVIDE ALL DIMENSIONS FOR RESTROOM LOCATED IN THE |
| | CENTER OF THE SPACE AND SHOW THE TURNING SPACE REQUIRED |
| | BY SEC. 603.2.1 FBC-ACCESSIBILITY. |
| | |
| | C) SHOW THE TURNING SPACE REQUIRED BY SEC. 603.2.1 |
| | FBC-ACCESSIBILITY FOR THE OTHER RESTROOM. |
| | |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| | REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. |
| | |
| | |