| 2018-05-09 17:14:43 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18041299 |
| | 5/9/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS C-1 & 4.0M: MECHANICAL NOTES #1 & #5 ON C-1 |
| | SEEM TO INDICATE (3) 5-TON AC SYSTEMS WILL BE |
| | INSTALLED, HOWEVER THE PLAN SHOWS (2). |
| | |
| | 2) REPLACEMENT OF THE AC SYSTEMS ARE NOT EXACT SAME |
| | SIZE REPLACEMENTS SO COOLING AND HEATING CALCULATIONS |
| | ARE REQUIRED TO VERIFY ACCURATE SIZING- SECTION |
| | C403.2.1 FBC-14 ENERGY CONSERVATION. |
| | |
| | 3) 4.0M: PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION |
| | OF THE NEW ROOFTOP UNITS ON THE EXISTING CURBS. IF |
| | USING CURB ADAPTERS PLEASE INCLDUE THEM IN THE DETAILS |
| | AND SUBMIT SPECS- SECTION 301.15 FBC-17 MECHANICAL. |
| | |
| | 4) SHEET C-1, NOTE 3 & SHEET 4.0M: SHOW THE LOCATIONS |
| | OF THE ROOFTOP HOODS AND PROVIDE CAPPING DETAILS. |
| | |
| | 5) 4.0M: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| | SUPPLY SYSTEMS OF THE NEW 5-TON RTU'S , UNLESS |
| | MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEMS |
| | CANNOT PRODUCE OVER 2000 CFMS OF SUPPLY AIR- SECTION |
| | 606.2.1. |
| | |
| | 6) ONE SET OF PLANS IS MISSING THE 4.0M SHEET. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |