| 2018-09-17 10:00:18 | |
| | 2ND REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED. |
| | |
| | 1) SHT. A2.02 - THE SINK IN THE PREASSEMBLY ROOM NEXT |
| | TO ROOM #220 SHALL COMPLY WITH THE 2014 |
| | FBC-ACCESSIBILITY SECS. 212.3, 606.2, 606.3, 606.4.THE |
| | MAXIMUM HEIGHT OF THE COUNTERTOP/SINK SHALL BE A |
| | MAXIMUM OF 34 INCHES ABOVE THE FINISH FLOOR PER THE |
| | 2014 FBC-ACCESS. SEC. 606.3.//// THE RESPONSE LETTER |
| | REFERS TO DETAIL # 1 ON SHT. ID. 5.13 I COULD NOT |
| | LOCATE THAT SHEET IN THIS SUBMITTAL IT APPEARS TO BE |
| | MISSING PLEASE INDICATE ON THE PLAN THE REQUIRED CLEAR |
| | FLOOR SPACE AND THE SINK HEIGHT. |
| | |
| | 2) SHTS. A7.05 & A.7.41, DETAIL #14 - TOILET ROOM # 622 |
| | - THE LAVATORY APPEARS TO BE ENCROACHING INTO THE 60 |
| | INCH CLEAR FLOOR SPACE FOR THE WATER CLOSET. NO FIXTURE |
| | MAY ENCROACH INTO THIS CLEAR FLOOR SPACE PER 2014 |
| | FBC-ACCESS. SEC.604.3.2. //// THE RESPONSE TO THIS |
| | COMMENT DOES NOT COMPLY WITH THE CODE DUE TO THE |
| | OCCUPANT LOAD SEPARATE FACILITIES ARE REQUIRED AND BOTH |
| | SHALL COMPLY WITH ACCESSIBILITY. PER FBC PL 403.2 AND |
| | FBC ACC 213.1 |
| | |
| | 4) SUBMIT TWO COPIES OF COMPLETE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE AUTO-FUEL FILL MINI-SMART PUMP. |
| | WPB AMEND. TO FBC SEC. 107.2.1.//// COMPLETE |
| | SPECIFICATION AND INSTALLATION GUIDE IS REQUIRED THE |
| | DETAIL ON THE PLAN IS JUST A GENERAL DRAWING AND DOES |
| | NOT HAVE ANY DETAIL SUCH AS THE UL RATING OF THE MOTOR |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | |