| 2018-09-29 14:27:11 | **CORRECTIONS** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. EFFECTIVE JULY 1, 2018, SUBMITTALS OVER 25 PAGES ARE |
| | TO BE DIGITAL. RESUBMITTAL FOR THIS REVISION IS TO BE |
| | DIGITAL, ALL AFFECTED PAGES. |
| | |
| | 2.FOR THIS REVISION, TWO OLD SETS WERE REMOVED. ONE OLD |
| | SET WAS LEFT, THREE NEW SETS SUBMITTED. THE THREE NEW |
| | SETS ARE LACKING THE PAGES WHICH WERE NOT REVISED; |
| | THESE PAGES SHOULD HAVE BEEN REMOVED FROM THE OLD SETS |
| | AND INSERTED INTO THE NEW SETS. THEREFORE, THE SETS I |
| | HAVE ARE INCOMPLETE. FOR A FEW EXAMPLES, THE FOLLOWING |
| | PAGES ARE MISSING FROM THE REVISION: |
| | |
| | ALL CIVIL PAGES (NEEDED FOR REFERENCE) |
| | SEVERAL LANDSCAPE PAGES (NOT CLEAR IF THIS IS NEEDED, |
| | BUT A PARTIAL LANDSCAPE SHOULD NOT BE IN THE PACKAGE - |
| | SHOULD BE EITHER COMPLETE OR REMOVED) |
| | A1.13 |
| | A1.15 |
| | A1.17 |
| | A1.18 |
| | |
| | 3. THE ISSUE WITH THE MISSING SHEETS APPEAR TO BE AN |
| | ISSUE FOR FMEP SHEETS AS WELL AS A AND S SHEETS. |
| | THEREFORE IT IS NOT POSSIBLE TO ISSUE MECHANICAL AND |
| | ELECTRICAL, BOTH WHICH HAVE PASSED, AS PREVIOUSLY |
| | OFFERED. |
| | |
| | 4. LANDSCAPE PAGES WERE SUBMITTED. LANDSCAPING IS A |
| | SEPARATE PERMIT. IT APPEARS THAT 17060986 IS READY FOR |
| | ISSUANCE BUT HAS NOT BEEN PICKED UP. SINCE IT HAS NOT |
| | BEEN ISSUED, IF THERE ARE LANDSCAPE REVISIONS, YOU CAN |
| | RESUBMIT WITH UPDATED SHEETS RATHER THAN HAVE THE |
| | PERMIT ISSUED. |
| | |
| | 5. ON REVISION 6, REVISION CLOUDS 4, 5 WERE REMOVED. TO |
| | PROPERLY DOCUMENT ALL CHANGES IN WHAT OUR PERMIT RECORD |
| | CONSIDERS ONE REVISION, PLEASE INCLUDE ALL CLOUDS 4, 5, |
| | 6 AND (ADDRESSING NEW COMMENTS) 7. |
| | |
| | 6. SHEET A1.13, A8.03, A8.04 ARE REFERENCED IN THE |
| | NARRATIVE BUT WAS NOT PROVIDED, PLEASE CORRELATE. |
| | |
| | 7. SHEET A1.16 WAS SUBMITTED WITH A DELTA 6 BUT I WAS |
| | UNABLE TO LOCATE THIS REVISION AND IT'S NOT INCLUDED IN |
| | THE NARRATIVE, PLEASE CORRELATE. |
| | |
| | 8. A2.04, ROOM 407, FBC B 307.1.1, A NEW FUEL TANK IN A |
| | NEW ROOM IS SHOWN. NO FIRE RATING IS SHOWN. NO |
| | INFORMATION REGARDING THE TANK, AMOUNT OF FUEL, |
| | OCCUPANCY CLASSIFICATION, WAS PROVIDED. |
| | |
| | REVISE PLAN TO INCLUDE OCCUPANCY CLASSIFICATION FOR |
| | THIS NEW ROOM. SEE FBC B TABLE 307.1, FOOTNOTE P, FUEL |
| | IN THE TANK AND IN VEHICLES ARE EXEMPT, BUT FUEL STORED |
| | SEPARATELY TO FUEL AN APPLIANCE DOES NOT APPEARS TO BE |
| | EXEMPT. FBC 107, THERE IS NOT ENOUGH INFORMATION TO |
| | PROVIDE A COMPLETE REVIEW. REVISE PLAN TO SHOW CLASSIFY |
| | AS HAZARDOUS OR SHOW AMOUNT ALLOWED UNDER FBC B TABLE |
| | 307.1(1). |
| | |
| | 9. ARCHITECTURAL PAGE PROPOSES NO FIRE RATING FOR NEW |
| | ROOM 407 FUEL TANK, SHEET P2.06 SHOWS A 3 HOUR RATING; |
| | PLEASE CORRELATE. |
| | |
| | 10. THE TOILET EXHAUST WHICH WAS PREVIOUSLY GOING |
| | THROUGH STAIR 1, 6TH LEVEL, WAS REROUTED BUT NOW |
| | PLUMBING PIPING IS IN THE STAIR, SEPARATED BY A |
| | HORIZONTAL SHAFT WALL. |
| | |
| | PER BUILDING OFFICIAL, THIS CONDITION IS ACCEPTABLE BUT |
| | PROVIDE THE FOLLOWING INFORMATION: |
| | |
| | PENETRATION DETAIL FOR THE WALL |
| | PENETRATION DETAIL FOR THE FLOOR |
| | SPECIFIC HORIZONTAL SHAFT ASSEMBLY |
| | |
| | 11. A7.43 SHOWS FIRE RATING DETAILS, BUT THEY APPEAR |
| | NON-SYMMETRICAL. IF THEY ARE NON SYMMETRICAL, THEY ARE |
| | TO BE TESTED FROM BOTH SIDES. SEE ALSO FLORIDA DEC |
| | STATEMENT DS2016-078. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |