| Plan Review Notes For Permit 18041294 |
| Permit Number |
18041294 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-26 05:03:56 | 1) SHT. A2.02 - THE SINK IN THE PREASSEMBLY ROOM NEXT | | | TO ROOM #220 SHALL COMPLY WITH THE 2014 | | | FBC-ACCESSIBILITY SECS. 212.3, 606.2, 606.3, 606.4.THE | | | MAXIMUM HEIGHT OF THE COUNTERTOP/SINK SHALL BE A | | | MAXIMUM OF 34 INCHES ABOVE THE FINISH FLOOR PERR THE | | | 2014 FBC-ACCESS. SEC. 606.3. | | | 2) SHTS. A7.05 & A.7.41, DETAIL #14 - TOILET ROOM # 622 | | | - THE LAVATORY APPEARS TO BE ENCROACHING INTO THE 60 | | | INCH CLEAR FLOOR SPACE FOR THE WATER CLOSET. NO FIXTURE | | | MAY ENCROACH INTO THIS CLEAR FLOOR SPACE PER 2014 | | | FBC-ACCESS. SEC.604.3.2. | | | 3) THE SUBMITTED NARRATIVE LISTS SHT.P5.02 - THIS SHEET | | | IS NOT INCLUDED IN THE SET OF PLANS.SUBMIT THIS SHEET | | | FOR REVIEW AS IT CONTAINS THE CHANGES TO THE BOILER | | | ROOM EQUIPMENT. | | | 4) SUBMIT TWO COPIES OF COMPLETE MANUFACTURER'S | | | SPECIFICATIONS FOR THE AUTO-FUEL FILL MINI-SMART PUMP. | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | |
|