| 2018-06-29 13:33:50 | 4TH REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18041247 |
| | 6/29/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) COMMENT #6 FROM THE 3RD REVIEW HAS NOT BEEN |
| | COMPLETELY ADDRESSED- "LABS"ARE STILL SHOWN ON THE LIFE |
| | SAFETY PLAN, AND ALL OF THE ARCHITECTURAL PLANS. EITHER |
| | MATCH ALL ROOM ID'S ON THOSE PLAN SHEETS WITH THE MEP |
| | PLAN SHEETS, OR AS PREVIOUSLY REQUESTED, PROVIDE AN |
| | EXHAUST SYSTEM FOR THE LAB ROOM PER TABLE 403.3.1.1. |
| | SEE PREVIOUS COMMENT #6 BELOW. |
| | |
| | 6) THE LIFE SAFETY PLAN ALS1.1, AND ARCHITECTURAL, |
| | PLUMBING AND ELECTRICAL PLANS ARE IDENTIFYING THE LARGE |
| | WORK AREA AS A "LAB" WHICH CONFLICTS WITH THE |
| | ARCHITECT'S ASSERTION THAT THIS IS A WORK AREA. REFER |
| | TO SECTIONS 510.1 AND 510.2 FBC M AND PROVIDE A LIST OF |
| | ALL CHEMICALS AND THEIR QUANTITIES TO BE USED AND |
| | STORED AT THE FACILITY AND PROVIDE MSDS SHEETS FOR |
| | EACH. PLEASE NOTE A HAZARDOUS EXHAUST SYSTEM MAY BE |
| | REQUIRED PER SECTION 510.2. IF THE WORK AREA IS NOT |
| | CONSIDERED A "LAB" PLEASE CORRECTLY IDENTIFY THE ROOM |
| | ON ALL PLAN SHEETS AND PROVIDE A NARRATIVE THAT |
| | CLARIFIES WHAT PROCESSES TAKE PLACE IN THE ROOM, AND |
| | WHAT, IF ANY CHEMICALS AND THEIR QUANTITIES ARE USED IN |
| | THE PROCESSES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |