| 2018-06-14 11:28:50 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18041247 |
| | 6/14/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M6.1: REFER TO SECTION 403.3.1.1 AND TABLE |
| | 403.3.1 AND REVISE THE O/A CALCULATIONS TO INCLUDE THE |
| | WORK AREA, THE MACHINE AND PLASTER ROOMS. THE MOST |
| | SIMILAR OCCUPANCY IN THE TABLE WOULD BE WOOD/METAL |
| | SHOPS WHICH REQUIRES O/A RATES BASED ON (20 PERSONS PER |
| | 1000 SQ. FT.) AT (10 CFMS PER PERSON) AND (0.18 CFMS |
| | PER SQ. FT.). PLEASE SEE FOOTNOTE G WHICH PROHIBITS |
| | RECIRCULATION OF AIR FROM THOSE ROOMS AND SPACES. |
| | UPDATE THE 2014 CODE REFERENCE LISTED UNDER THE TABLE |
| | TO THE 2017 EDITION OF THE MECHANICAL CODE. |
| | |
| | 2) SHEET M2.1 & M6.1: PLEASE LABEL OR IDENTIFY ALL OF |
| | THE WORK ROOMS SO THEY MATCH THE IDENTIFICATIONS LISTED |
| | IN THE AIR BALANCE SCHEDULE. |
| | |
| | 3) M6.1: PROVIDE EXHAUST VENTILATION CALCULATION PER |
| | TABLE 403.3.1 FBC M WHICH REQUIRES A RATE OF 0.50 CFMS |
| | PER SQ. FT. FOR THE WORK AND MACHINE ROOMS. |
| | |
| | 4) M2.1: AS NOTED IN COMMENT #1 ABOVE, RECIRCULATION OF |
| | AIR FROM THE WORK ROOM, MACHINE ROOM ETC. IS PROHIBITED |
| | EXCEPT THAT RECIRCULATION SHALL BE PERMITTED WHERE THE |
| | RESULTING SUPPLY AIRSTREAM CONSISTS OF NOT MORE THAN 10 |
| | PERCENT AIR RECIRCULATED FROM THESE SPACES. PLEASE |
| | REVISE THE LAYOUT PLAN ACCORDINGLY. |
| | |
| | 5) M6.1: REFER TO SECTION 501.4 FBC M AS IT APPLIES TO |
| | THE MACHINE ROOM WHICH APPEARS NOT TO BE AT NEUTRAL OR |
| | NEGATIVE PRESSURE. PLEASE NOTE THAT THE AIR BALANCE |
| | TABLE IS ALSO NOT SHOWING ANY TRANSFER AIR CFMS. |
| | |
| | 6) THE LIFE SAFETY PLAN ALS1.1, AND ARCHITECTURAL, |
| | PLUMBING AND ELECTRICAL PLANS ARE IDENTIFYING THE LARGE |
| | WORK AREA AS A "LAB" WHICH CONFLICTS WITH THE |
| | ARCHITECT'S ASSERTION THAT THIS IS A WORK AREA. REFER |
| | TO SECTIONS 510.1 AND 510.2 FBC M AND PROVIDE A LIST OF |
| | ALL CHEMICALS AND THEIR QUANTITIES TO BE USED AND |
| | STORED AT THE FACILITY AND PROVIDE MSDS SHEETS FOR |
| | EACH. PLEASE NOTE A HAZARDOUS EXHAUST SYSTEM MAY BE |
| | REQUIRED PER SECTION 510.2. IF THE WORK AREA IS NOT |
| | CONSIDERED A "LAB" PLEASE CORRECTLY IDENTIFY THE ROOM |
| | ON ALL PLAN SHEETS AND PROVIDE A NARRATIVE THAT |
| | CLARIFIES WHAT PROCESSES TAKE PLACE IN THE ROOM, AND |
| | WHAT, IF ANY CHEMICALS AND THEIR QUANTITIES ARE USED IN |
| | THE PROCESSES. |
| | |
| | 7) PLEASE CLARIFY THE PURPOSE OF THE NEW FIRE DAMPERS |
| | TO BE INSTALLED WHERE THE EXISTING DUCT IS PENETRATING |
| | THE OFFICE 122 WALLS. THE ARCHITECTURAL PLANS ARE NOT |
| | SHOWING THESE WALLS TO BE FIRE-RATED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |