Plan Review Notes
Plan Review Notes For Permit 18041247
Permit Number 18041247
Review Stop M
Sequence Number 1
Notes
Date Text
2018-05-24 16:54:331ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18041247
 5/24/18
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE MECHANICAL PLANS INCLUDING MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES, A
 DUCT LAYOUT PLAN SHOWING ALL NEW AND RELOCATED DUCTS
 AND DIFFUSERS, AND AN AIR DISTRIBUTION SCHEDULE FOR ALL
 NEW DUCTS, DIFFUSERS, AND RETURN GRILLS TO BE
 INSTALLED.
  
 2) THE PLANS INDICATE A NEW LAB TO BE INSTALLED WHICH
 WILL REQUIRE INSTALLATION OF AN EXHAUST VENTILATION
 SYSTEM WITH AN EXHAUST AIRFLOW RATE OF 1.0 CFMS PER SF.
 RECIRCULARION OF AIR FROM THE SPACE IS PROHIBITED WITH
 AN EXCEPTION OF NOT MORE THAN 10% OF THE AIRFLOW STREAM
 FROM THE LAB- SEE FOOTNOTE G. PLEASE NOTE THAT EXHAUST
 VENTILATION SYSTEMS MAY BE REQUIRED FOR ALL OTHER ROOMS
  
 STORING OR PROCESSING CHEMICALS OR MATERIALS THAT GIVE
 OFF DUSTS OR FUMES- PLEASE REFER TO SECTION 414 FBC BC,
 AND SECTION 502.1 FBC MC:
  
 502.1 GENERAL.AN EXHAUST SYSTEM SHALL BE PROVIDED,
 MAINTAINED AND OPERATED AS SPECIFICALLY REQUIRED BY
 THIS SECTION AND FOR ALL OCCUPIED AREAS WHERE MACHINES,
 VATS, TANKS, FURNACES, FORGES, SALAMANDERS AND OTHER
 APPLIANCES, EQUIPMENT AND PROCESSES IN SUCH AREAS
 PRODUCE OR THROW OFF DUST OR PARTICLES SUFFICIENTLY
 LIGHT TO FLOAT IN THE AIR, OR WHICH EMIT HEAT, ODORS,
 FUMES, SPRAY,
  
 GAS OR SMOKE, IN SUCH QUANTITIES SO AS TO BE IRRITATING
 OR INJURIOUS TO HEALTH OR SAFETY.
  
 THE MECHANICAL REVIEW IS STOPPED AT THIS POINT PENDING
 SUBMITTAL OF COMPLETE PLANS AND SPECIFICATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  