| 2018-05-24 16:54:33 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18041247 |
| | 5/24/18 |
| | |
| | CODES IN EFFECT: |
| | FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE MECHANICAL PLANS INCLUDING MINIMUM |
| | VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES, A |
| | DUCT LAYOUT PLAN SHOWING ALL NEW AND RELOCATED DUCTS |
| | AND DIFFUSERS, AND AN AIR DISTRIBUTION SCHEDULE FOR ALL |
| | NEW DUCTS, DIFFUSERS, AND RETURN GRILLS TO BE |
| | INSTALLED. |
| | |
| | 2) THE PLANS INDICATE A NEW LAB TO BE INSTALLED WHICH |
| | WILL REQUIRE INSTALLATION OF AN EXHAUST VENTILATION |
| | SYSTEM WITH AN EXHAUST AIRFLOW RATE OF 1.0 CFMS PER SF. |
| | RECIRCULARION OF AIR FROM THE SPACE IS PROHIBITED WITH |
| | AN EXCEPTION OF NOT MORE THAN 10% OF THE AIRFLOW STREAM |
| | FROM THE LAB- SEE FOOTNOTE G. PLEASE NOTE THAT EXHAUST |
| | VENTILATION SYSTEMS MAY BE REQUIRED FOR ALL OTHER ROOMS |
| | |
| | STORING OR PROCESSING CHEMICALS OR MATERIALS THAT GIVE |
| | OFF DUSTS OR FUMES- PLEASE REFER TO SECTION 414 FBC BC, |
| | AND SECTION 502.1 FBC MC: |
| | |
| | 502.1 GENERAL.AN EXHAUST SYSTEM SHALL BE PROVIDED, |
| | MAINTAINED AND OPERATED AS SPECIFICALLY REQUIRED BY |
| | THIS SECTION AND FOR ALL OCCUPIED AREAS WHERE MACHINES, |
| | VATS, TANKS, FURNACES, FORGES, SALAMANDERS AND OTHER |
| | APPLIANCES, EQUIPMENT AND PROCESSES IN SUCH AREAS |
| | PRODUCE OR THROW OFF DUST OR PARTICLES SUFFICIENTLY |
| | LIGHT TO FLOAT IN THE AIR, OR WHICH EMIT HEAT, ODORS, |
| | FUMES, SPRAY, |
| | |
| | GAS OR SMOKE, IN SUCH QUANTITIES SO AS TO BE IRRITATING |
| | OR INJURIOUS TO HEALTH OR SAFETY. |
| | |
| | THE MECHANICAL REVIEW IS STOPPED AT THIS POINT PENDING |
| | SUBMITTAL OF COMPLETE PLANS AND SPECIFICATIONS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |