Plan Review Notes
Plan Review Notes For Permit 18041240
Permit Number 18041240
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-05-15 15:31:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO INDICATION OF COMPLIANCE WITH ANY FIRE
 CODE.
  
 THE INSTALLATION SHALL COMPLY WITH NFPA? 110 STANDARD
 FOR EMERGENCY AND STANDBY POWER SYSTEMS
 2013 EDITION
  
 PLEASE REVIEW TO ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE.
  
  
  
  
 2) THERE IS NO INDICATION OF THE SEPARATION DISTANCE
 FROM AND NEARBY BUILDINGS TO ENSURE NO EXPSOURE TO
 EXHAUST FUUMES.
  
 PLEASE PROVIDE DISTANCES AS APPLICABLE ON THE SITE
 PLAN.
  
 PER NFPA 110
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
  
  
  
 3) THERE IS NO INDICATION IF YOUR BUILDING IS PROVIDED
 WITH ANY FIRE ALARM OR FIRE SPRINKLER SYSTEMS THAT MAY
 NEED TO BE TIED INTO THIS GENERATOR.
  
 PLEASE PROVIDE AN APPLICABLE NOTE AS THE TIE HAS TO BE
 DONE BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  