2018-05-14 17:47:20PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE WIND LOAD DATA ON THE PLANS. FBC
 1603.1.4
  
 2) SUBMIT TWO SETS OF STRUCTURAL DETAILS FOR THE
 CONCRETE SLAB THAT WILL SUPPORT THE NEW GENERATOR. FBC
 107.2.1 & 1604.1
  
 2) SPECIFY THE FASTENERS (TYPE, SIZE, EMBED DEPTH,
 ETC.) THAT WILL BE USED TO ANCHOR THE GENERATOR TO TO
 THE SLAB TO PREVENT SLIDING AND OVERTURN FROM
 WINDLOADING. FBC 107.2.1 & 1604.1
  
  