| Plan Review Notes For Permit 18041240 |
| Permit Number |
18041240 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-14 17:47:20 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY THE WIND LOAD DATA ON THE PLANS. FBC | | | 1603.1.4 | | | | | | 2) SUBMIT TWO SETS OF STRUCTURAL DETAILS FOR THE | | | CONCRETE SLAB THAT WILL SUPPORT THE NEW GENERATOR. FBC | | | 107.2.1 & 1604.1 | | | | | | 2) SPECIFY THE FASTENERS (TYPE, SIZE, EMBED DEPTH, | | | ETC.) THAT WILL BE USED TO ANCHOR THE GENERATOR TO TO | | | THE SLAB TO PREVENT SLIDING AND OVERTURN FROM | | | WINDLOADING. FBC 107.2.1 & 1604.1 | | | | | | |
|