| Plan Review Notes For Permit 18041239 |
| Permit Number |
18041239 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-06-14 17:07:11 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | GENERATOR PAD AND ANCHORING | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | COMMENTS FROM THE PREVIOUS REVIEWS HAVE NOT BEEN | | | ADDRESSED. | | | | | | 1) FBC 107.2.1 & R301.1 SUBMIT TWO SETS OF GENERATOR | | | ANCHORING AND PAD PLANS. ( THE GENERATOR PAD DOCUMENTS | | | THAT WERE SUBMITTED INDICATE THAT THE 4 INCH THICK PADS | | | HAVE A WIND RATING OF 175 MPH. HOWEVER, THE ONE THAT IS | | | HIGHLIGHTED ON THE SECOND PAGE IS THE 3 INCH PAD | | | WITHOUT A WIND RATING. YOU WILL BE REQUIRED TO SUBMIT | | | THE TESTING FROM AN APPROVED TESTING AGENCY OR A | | | FLORIDA LICENSED ENGINEER'S SIGNED AND SEALED | | | CALCULATIONS WHICH SHOW THAT THE 4 INCH PAD IS RATED | | | FOR 175 MPH.) | | | | | | 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | |
|