 GENERATOR PAD AND ANCHORING
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 COMMENTS FROM THE PREVIOUS REVIEWS HAVE NOT BEEN
 ADDRESSED.
  
 1) FBC 107.2.1 & R301.1 SUBMIT TWO SETS OF GENERATOR
 ANCHORING AND PAD PLANS. ( THE GENERATOR PAD DOCUMENTS
 THAT WERE SUBMITTED INDICATE THAT THE 4 INCH THICK PADS
 HAVE A WIND RATING OF 175 MPH. HOWEVER, THE ONE THAT IS
 HIGHLIGHTED ON THE SECOND PAGE IS THE 3 INCH PAD
 WITHOUT A WIND RATING. YOU WILL BE REQUIRED TO SUBMIT
 THE TESTING FROM AN APPROVED TESTING AGENCY OR A
 FLORIDA LICENSED ENGINEER'S SIGNED AND SEALED
 CALCULATIONS WHICH SHOW THAT THE 4 INCH PAD IS RATED
 FOR 175 MPH.)
  
 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  