| Plan Review Notes For Permit 18041222 |
| Permit Number |
18041222 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-22 13:31:12 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. SHEET S1-101 REFERS TO A SOILS REPORT, PLEASE | | | PROVIDE, FBC 107. | | | | | | 2. A RESIDENT INSPECTOR IS REQUIRED FOR THE BOLTS AND | | | WELDS, FBC 110. | | | | | | 3. WHO WILL MONITOR THE AUGERCAST PILE INSTALLATION? | | | PROVIDE A LETTER, FBC 110. | | | | | | 4. REVISE PLAN TO INCLUDE COMPONENT & CLADDING | | | PRESSURES, FBC B 1603.1.4. | | | | | | 5. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING | | | PROVISO: STANDING SEAM PRODUCT APPROVAL IS REQUIRED TO | | | BE REVIEWED BY DESIGNER OF RECORD, SUBMITTED TO THE | | | BUILDING DIVISION, REVIEWED AND ISSUED PRIOR TO | | | INSTALLATION. | | | | | | | | | |
|