| Date |
Text |
| 2018-06-15 13:08:04 | ****CORRECTIONS**** |
| | COURTESY REVIEW TO FURTHER CLARIFY PLAN REVIEW ISSUES |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. FBC B CHAPTER 10, FBC ACCESSIBILITY, MEANS OF EGRESS |
| | NOT CLEAR. REVISE PLAN TO SHOW COMPLIANCE WITH, OR |
| | CLARIFY; 1-A1.101, CONSTRUCTION PLAN - PLAZA, DOES NOT |
| | SHOW ALL EXIT DOORS AND THE ACCESSIBLE ROUTE. THERE ARE |
| | PARALLEL LINES AT THE EAST LOBBY EXIT DOOR; ARE THESE |
| | STAIRS? IF NOT STAIRS, WHAT DO THE LINES DEPICT? THERE |
| | IS A "TENANT SPACE" AREA TO THE WEST OF THE PLAZA, |
| | APPEARS TO INCLUDE SIX EXIT DOORS, BUT THE DOORS ARE |
| | EXCLUDED FROM THE "ACCESSIBLE ROUTE". FBC 107. |
| | |
| | 2. A-1.01, NOTE 22 IS "NEW STEPS, SEE LANDSCAPE". NOTE |
| | 17 IS "NEW ACCESSIBLE CONCRETE RAMP". PLEASE REVISE |
| | PLAN TO INCLUDE THE FOLLOWING: |
| | |
| | 1-LS2.03 HAS DETAILS FOR RAMP AND STAIR. THERE IS A |
| | NOTE POINTING TO THE STAIR, "REINFORCING, REF |
| | STRUCTURAL"; ANOTHER NOTE WHICH STATES "COMPACTED SUB |
| | GRADE PER GEOTECH OR CIVIL RECOMMENDATION". WHERE ON |
| | THE CIVILS? PLEASE PROVIDE SOILS REPORT IF IT'S DESIGN |
| | TEAM'S INTENT THAT A SOILS REPORT SPECIFIES SOIL |
| | COMPACTION. |
| | |
| | ADVISE WHERE THE STRUCTURAL DETAIL FOR THE RAMP CAN BE |
| | LOCATED ON STRUCTURAL PLAN, OR REVISE PLAN TO INCLUDE. |
| | |
| | 3. REVISE PLAN TO CLEARLY SHOW THE RISE AND WIDTH OF |
| | RAMPS AND STAIRS. IT IS NOT CLEAR IF TWO OR MORE |
| | HANDRAILS ARE REQUIRED. HANDRAIL IS SHOWN ON THE DETAIL |
| | BUT NOT ON THE PLAN. |
| | |
| | 4. REVISE PLAN TO PROVIDE A PLAN FOR THE RAMP WHICH |
| | SHOWS LANDINGS, TURNS IF APPLICABLE, RUN DIMENSION. |
| | |
| | 5. RAMPS AND STAIRS ARE NOT SHOWN ON S1.101 "STRUCTURAL |
| | AREA OF WORK PLAN". IT APPEARS THAT A STRUCTURAL DETAIL |
| | FOR RAMP IS REQUIRED. |
| | |
| | SEE FBC A 405, 504, 505, FBC B CHAPTER 10, FBC 107 |
| | |
| | |