| Plan Review Notes For Permit 18041162 |
| Permit Number |
18041162 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-06-04 03:54:50 | 1) SHOW THE DISTANCE FROM THE OUTLET OF THE GAS METER | | | TO THE INLET OF THE MP REGULATOR FOR THE EXISTING | | | INTERIOR LOAD ON THAT SECTION.2017 FBC-FUEL GAS SEC. | | | 402.4.1. | | | 2) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE | | | CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 3) SHOW THE DISTANCE FROM THE OUTLET OF THE MP | | | REGULATOR TO THE MOST REMOTE OUTLET ON THE INTERIOR | | | SECTION OF THE SYSTEM.2017 FBC-FUEL GAS SEC.402.4.1. | | | THE EXISTING GAS PLANS ON FILE AT THE CITY SHOW THE | | | MOST REMMOTE OUTLET AT 83 FEET FROM THE METER. CLARIFY. | | | 4) THE SHUTOFF VALVE ON THE EXISTING PIPING TO THE | | | INTERIOR SHALL BE LOCATED IMMEDIATELY AHEAD OF THE | | | REGULATOR PER 2017 FBC-FUEL GAS SEC. 409.4. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | |
|