| Date |
Text |
| 2018-05-15 05:26:00 | |
| | 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF |
| | THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1. |
| | 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE TO THE |
| | REGULATOR SERVING THE EXISTING GAS LOAD.WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 3) SHOW THE TYPE OF PIPE AND PIPE SIZE DOWNSTREAM OF |
| | THE REGULATOR FOR THE EXISTING GAS LOADS AND NOTE THE |
| | DISTANCE FROM THIS REGULATOR TO THE FURTHEST OUTLET ON |
| | THAT SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 4) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD |
| | OF THE MP REGULATOR FFOR THE EXISTING LOADS.. 2017 FBCR |
| | SEC. G2420.4. |
| | 5) SPECIFY ON THE GAS DRAWING HOW THE 3/4 INCH |
| | GALVANIZED PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND |
| | PIPING OUTDOORS SHALL COMPLY WITH 2017 FBCR |
| | SEC.G2415.9, G2415.11. |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX |
| | CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL |
| | BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE |
| | GENERATOR. 2017 FBCR SEC. G2422.1 (8). |
| | 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017 |
| | FBCR SEC.G2419.4. |
| | 8) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE |
| | CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND. |
| | TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1. |
| | 9) SUBMIT CLEAR AND LEGIBLE SPECIFICATIONS FOR THE |
| | GENERATOR. SOME AREAS ON THE SHEETS CANNOT BE READ. WPB |
| | AMEND. TO FBC SEC. 1107.2.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |