| 2018-06-29 12:56:38 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. ANY MODIFICATION OF BRANCH CIRCUITS THAT SUPPLY |
| | 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS |
| | INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS, |
| | LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, |
| | SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS, |
| | LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI |
| | PROTECTED. PROVIDE CORRECTION. NEC 210.12; FBC RE |
| | E3902.16 (AFCI NOTE PROVIDED DOES NOT COVER ALL AREAS |
| | THAT REQUIRE AFCI PROTECTION AS NOTED ABOVE. PROVIDE |
| | CORRECTION.) |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE |
| | EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC |
| | RE R314.3, R315.1; WPB FBC 107.2.1 (SMOKE ALARMS MUST |
| | BE INSTALLED AT LEAST 3 FEET FROM BATHROOM DOOR, 3 FEET |
| | FROM CEILING FANS, AND 3 FEET FROM ANY MECHANICAL DUCT. |
| | PROVIDE CORRECTIONS. FBC RE R314.3(4), NFPA |
| | 72:29.8.3.4) |
| | 8. CORRECTED. |
| | 9. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP |
| | CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. |
| | PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE |
| | E3703.4, E3901.6 (ONE OF THE BATHROOMS SHOWS ONLY ONE |
| | GFCI RECEPTACLE, BUT THERE ARE TWO BASINS. THE |
| | RECEPTACLE SHOWN IS NOT WITHIN THREE FEET OF THE SECOND |
| | BASIN. PROVIDE CORRECTION.) |
| | |
| | NEW COMMENTS: |
| | |
| | 10. RECEPTALCE FOR GARAGE DOOR OPENER REQUIRES GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8; FBC RE |
| | E3902.2 |
| | 11. PANEL SCHEDULE SHOWS ONLY ONE SMALL APPLIANCE |
| | CIRCUIT. A MINIMUM OF TWO SMALL APPLIANCE CIRCUITS ARE |
| | REQUIRED FOR KITCHEN COUNTER RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 210.11(C)(1); FBC RE E3703.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |