Plan Review Notes
Plan Review Notes For Permit 18041079
Permit Number 18041079
Review Stop E
Sequence Number 1
Notes
Date Text
2018-05-01 07:17:24ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FBC 105.1 (PERMITS AND INSPECTIONS REQUIRED.
 ELEC-SUB PERMIT REQUIRED FOR EACH SIGN.
  
 2. CLARIFY IN SCOPE OF WORK WHICH SIGN IS FOR WHICH
 PERMIT.
  
 3. VALUE OF WIORK TOO LOW. PROVIDE COPY OF SIGNED
 CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL
 MATERIALS AND LABOR.
 FBC 109.3
  
 4. TIMECLOCK FOR SIGN MUST CONFORM TO FBC CE405.2.4 (IF
 INSTALLATION OF NEW TIMECLOCK IS NEEDED A SEPERATE
 ELECTRICAL PERMIT IS REQUIRED BY A CONTRACTOR HOLDING
 AN EC OR ER LICENSE.
  
 END OF COMMENTS.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN
 REVIEW COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO
 THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH
 EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 6TH EDITION, PART
 VIII ELECTRICAL
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 [email protected]
 561-657-1653