| Plan Review Notes For Permit 18041079 |
| Permit Number |
18041079 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-05-01 07:17:24 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. FBC 105.1 (PERMITS AND INSPECTIONS REQUIRED. | | | ELEC-SUB PERMIT REQUIRED FOR EACH SIGN. | | | | | | 2. CLARIFY IN SCOPE OF WORK WHICH SIGN IS FOR WHICH | | | PERMIT. | | | | | | 3. VALUE OF WIORK TOO LOW. PROVIDE COPY OF SIGNED | | | CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL | | | MATERIALS AND LABOR. | | | FBC 109.3 | | | | | | 4. TIMECLOCK FOR SIGN MUST CONFORM TO FBC CE405.2.4 (IF | | | INSTALLATION OF NEW TIMECLOCK IS NEEDED A SEPERATE | | | ELECTRICAL PERMIT IS REQUIRED BY A CONTRACTOR HOLDING | | | AN EC OR ER LICENSE. | | | | | | END OF COMMENTS. | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN | | | REVIEW COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO | | | PROVIDE A RESPONSE LETTER ADDRESSING | | | EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO | | | THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH | | | EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 6TH EDITION, PART | | | VIII ELECTRICAL | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | [email protected] | | | 561-657-1653 |
|